All initializations above are completely automatic when using st<strong>and</strong>ard <strong>Kollmorgen</strong><br />

motors.<br />

For MENCTYPE 0-2 <strong>and</strong> 7, ENCINIT should be performed where MENCOFF is<br />

unknown.<br />

Firmware Versions: All Type: switch mode (R/W) Units: N/A<br />

Range: 0 to 9<br />

Opmodes: All<br />

Default: motor data (0 if undefined) Drive Status: DIS<br />

EEPROM: Yes<br />

MFBDIR<br />

Sets the motor feedback direction. This switch is used during the Autoconfig process (see ACONFIG). If Phase<br />

5 of Autoconfig (Direction test) fails, MFBDIR can be used to switch the motor feedback direction. The range<br />

is 0 to 3:<br />

MFBDIR = 0: normal commutation direction, normal velocity direction.<br />

MFBDIR = 1: inverted commutation direction, normal velocity direction.<br />

MFBDIR = 2: normal commutation direction, inverted velocity direction.<br />

MFBDIR = 3: inverted commutation direction, inverted velocity direction.<br />

If the motor leads/motor stator are phased incorrectly, then setting MFBDIR=1 will solve the problem. If the<br />

feedback device is connected/phased incorrectly, you have to set MFBDIR=3, which changes both the<br />

commutation <strong>and</strong> velocity loop directions.<br />

Firmware Versions: 3.3.0 <strong>and</strong> later Type: switch mode (R/W) Units: N/A<br />

Range: 0 to 3 Default: 0 EEPROM: Yes<br />

Opmodes: All Drive Status: DIS<br />

MFOLD<br />

Displays the status of the motor foldback circuit. When the system current level exceeds MICONT for too long,<br />

the drive enters motor foldback mode, MFOLD changes from 0 to 1, <strong>and</strong> the drive current is limited gradually<br />

(in exponential fashion) to the value of MICONT. See also FOLD, FOLDMODE, MFOLDD, MFOLDDIS,<br />

MFOLDR, <strong>and</strong> MFOLDT.<br />

0 = motor foldback OFF (inactive)<br />

1 = motor foldback ON (drive is limiting output current)<br />

Firmware Versions: 3.2.0 <strong>and</strong> later Type: switch (R) Units: N/A<br />

Range: 0, 1 Default: 0 EEPROM: No<br />

Opmodes: All Drive Status: EN/DIS<br />

MFOLDD<br />

Sets the delay time for motor foldback. This is the amount of time that the system current can exceed MICONT<br />

before the drive will enter the motor foldback state. The time units assume a worst-case scenario where the drive<br />

is applying MIPEAK current. A current level of less than MIPEAK can be allowed for a longer time. See<br />

FOLD, FOLDMODE, MFOLD, MFOLDDIS, MFOLDR, <strong>and</strong> MFOLDT.<br />

Firmware Versions: 3.2.0 <strong>and</strong> later Type: variable (R/W) Units: seconds at MIPEAK<br />

Range: 1 to 2400 Default: 1200 EEPROM: Yes<br />

Opmodes: All Drive Status: EN/DIS<br />

60