Rail Corporation New South Wales<br />
<strong>Rolling</strong> <strong>Stock</strong> <strong>PPP</strong> – <strong>Double</strong> <strong>Deck</strong> <strong>Trains</strong><br />
Maintenance Facility Works Specification<br />
<strong>Exhibit</strong> 7 - MFS v7.doc<br />
on the Cars and the heaviest roof-mounted component of the existing <strong>RailCorp</strong><br />
electric fleet (2.5 tonnes) plus associated lifting frames, slings, etc. The cranes<br />
shall be interlocked in respect of location and the Overhead Traction Power<br />
System;<br />
(h) Maintenance Roads grades shall be designed such that rolling stock will not roll<br />
due to gravity;<br />
(i) elevated platforms shall be provided on both sides of each Maintenance Road<br />
for access to car equipment mounted at roof level. The design of these<br />
platforms must allow for removal and fitting of window glass. Adequate fall<br />
protection is to be provided in accordance with occupational health and safety<br />
laws;<br />
(j) access to elevated platforms shall be by fold-up stairs interlocked to prevent<br />
access whilst the Overhead Traction Power System is operational;<br />
(k) supply from the Overhead Traction Power System shall be provided to each<br />
Maintenance Road, with interlocking system and ‘swing away’ mounting of the<br />
Overhead Wire;<br />
(l) ‘Shore’ Supply 415 Volt, 3 phase 50 Hz AC power supply shall be provided to<br />
each Maintenance Road with outlets at regular intervals for the test operation of<br />
Car equipment;<br />
(m) 415 Volt, 3 phase 50 Hz power outlets shall be provided on both sides of each<br />
Maintenance Road for the operation of portable power tools and welders along<br />
the full length of each Maintenance Road;<br />
(n) 240 Volt, single phase power outlets shall be provided on both sides of each<br />
Maintenance Road at regular intervals for the operation of portable power tools<br />
and lights along the full length of each Maintenance Road;<br />
(o) access must be provided on all Maintenance Roads to enable presentation<br />
personnel to safely and efficiently access the sets for all cleaning work-<br />
including Major Cleans, Daily Cleans and Turnaround Cleans;<br />
(p) water supply points shall be provided on both sides of each Maintenance Road<br />
for cleaning operations along the full length of each Maintenance Road; and<br />
(q) reticulated general service compressed air supply is to be provided with ‘Quick<br />
Connect’ outlets on both sides of each Maintenance Road for the operation of<br />
pneumatic tools along the full length of each Maintenance Road.<br />
4.1.3 Underfloor Wheel Profiling Plant Building<br />
<strong>PPP</strong> Co must provide the Underfloor Wheel Profiling Plant Building to enclose the<br />
Underfloor Wheel Profiling Plant and associated equipment and facilities. As a minimum,<br />
the <strong>PPP</strong> Co design of the Underfloor Wheel Profiling Plant Building must incorporate the<br />
same features stipulated above for the Maintenance Building that are relevant to the<br />
Underfloor Wheel Profiling Plant’s physical and operational environments.<br />
v7 – 17/01/2011 Page 27 of 51