02.09.2014 Views

Medium Voltage Application Guide

Medium Voltage Application Guide

Medium Voltage Application Guide

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

13684.A<br />

Maximum cut-off current (kA) peak<br />

13682.A<br />

SWITCHGEAR<br />

Circuit Design (Motor circuit with fuses)<br />

A contactor always needs some form of back-up short circuit protection. Although circuit breakers can be used for<br />

this purpose, it is more common to use MV HRC fuses. Fuses have higher fault breaking capacity, are very fast acting<br />

and are a good current limiting device.<br />

Consider the following direct-on-line motor circuit, which includes a line contactor, short circuit protection fuses and<br />

a motor protection relay, providing overload protection. Assume an operating supply of 6.6 kV/50 Hz and a motor<br />

FLC of 120 A.<br />

Typical DOL circuit with contactor, fuses and relay<br />

6.6 kV /<br />

50 Hz<br />

F1<br />

K1<br />

CT1<br />

PR<br />

3<br />

M1<br />

M<br />

3<br />

(FLC = 120 A)<br />

Step 1: Select the contactor<br />

Rated voltage U r ≥ operating voltage U and AC3 rating I e ≥ motor FLC<br />

A 7.2 kV/50 Hz contactor with an AC3 rating of 200 A will be adequate<br />

Step 2: Select the fuse<br />

<br />

<br />

<br />

The manufacturer will specify the maximum allowable fuse size. As a general rule, the nominal rating of<br />

the fuse should be 1.5 times the motor FLC.<br />

In this case<br />

I (fuse) = 1.5 x 120<br />

= 180 A<br />

Use a 200 A fuse.<br />

On a time-current curve, check that the contactor thermal withstand curve lies outside the total clearing<br />

curve of the fuse.<br />

From the fuse cut-off curve, the "limited" prospective short circuit current of the fuse must be less than the<br />

short-time withstand current rating of the contactor.<br />

I sc' (fuse) ≤ I k (contactor)<br />

Assume the 7.2 kV/50 Hz, 200 A contactor has a short-time withstand current rating I k of 8 kA and the prospective<br />

rms fault current level I sc at the point of installation is 10 kA.<br />

100<br />

50<br />

20<br />

10<br />

315<br />

250<br />

200<br />

160<br />

100<br />

5<br />

63<br />

2<br />

1.0 2 5 10 20 50 100<br />

Prospective current (kA) rms<br />

From the fuse cut-off curve, we can see that a prospective rms fault current of 10 kA (I sc ) will be limited to 4 kA (I sc' )<br />

by the 200 A fuse. Check that I sc' (fuse) ≤ I k (contactor).<br />

4 kA ≤ 8 kA The fuse is suitable for use with the contactor.<br />

Page 98 <strong>Medium</strong> <strong>Voltage</strong> <strong>Application</strong> <strong>Guide</strong> 710-12280-00A

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!