SWITCHGEAR<br />

Transformer internal impedance, Z-int<br />

The internal impedance is 0.28 .<br />

Exercise<br />

Calculate the transformer's output terminal voltage drop if the load was drawing 6000 A (I-load).<br />

Internal voltage drop, U-int<br />

U-int<br />

I-load Z-int<br />

<br />

1000<br />

6000 0.28<br />

<br />

1000<br />

1680<br />

<br />

1000<br />

1.68 kV<br />

The internal voltage drop is 1.68 kV.<br />

Secondary output voltage due to<br />

overload, U r'<br />

r' E U-int<br />

7.33 1.68<br />

5.65 kV<br />

The secondary output voltage is 5.65 kV.<br />

Output voltage drop<br />

U r U r'<br />

The output voltage drop is 0.95 kV, or 14% U r<br />