SWITCHGEAR<br />

Step 3: Select an overload curve<br />

The nominal current setting of the curve is set for the motor FLC. In this case, set overload protection so<br />

that I n = 120 A<br />

The overload curve (hot curve) needs to lie outside the motor start curve and intersect with the fuse curve at a point<br />

before the maximum breaking current I c of the contactor.<br />

1<br />

3<br />

4<br />

5<br />

Motor FLC<br />

Motor start current<br />

Overload curve - nominal setting (In)<br />

Overload curve - hot<br />

Fuse total clearing curve<br />

Contactor maximum break current (Ic)<br />

Contactor thermal withstand curve<br />

2<br />

7<br />

6<br />

Current (A)<br />

710-12280-00A <strong>Medium</strong> <strong>Voltage</strong> <strong>Application</strong> <strong>Guide</strong> Page 99