SWITCHGEAR<br />

The calculated short circuit current of a transformer, I sc is often used to rate the downstream distribution switchgear<br />

it is feeding. In reality, the expected short circuit current at the switchgear installation will be less than the calculated<br />

short circuit current, due to any impedance in the feeder circuit (ie impedance of feeder cables, switchgear, busbars<br />

etc). All switchgear has a short-time withstand current rating (I k ), which is typically type tested for 3 seconds (t k ).<br />

I k > I sc<br />

Transformer<br />

Switchgear installation<br />

1<br />

I sc<br />

2<br />

Q1 Q2 Q3<br />

I k<br />

Example<br />

To calculate the short-time withstand current rating of the downstream switchgear, I k , we must calculate the rated<br />

secondary current and the short circuit current of the feeder transformer.<br />

Transformer power S = 20 MVA<br />

Secondary rated voltage U r = 11 kV<br />

Impedance Z% = 8%<br />

Assume infinite power system.<br />

Rated secondary current, I r<br />

r<br />

The transformer rated secondary current is 1050 A.<br />

Short circuit current, I sc<br />

r<br />

The transformer short circuit current is 13125 A.<br />

Switchgear rating, I k /t k<br />

I k I sc<br />

I k 13125 A<br />

An appropriate switchgear rating is 16 kA / 3 seconds.<br />