SWITCHGEAR<br />

Exercise<br />

Select the primary input fuses required to protect an 11 kV/400 VAC, 1000 kVA, 3-phase power transformer.<br />

The range of I n(FUSE) is 97.5~106 A. Use 100 A/12 kV, E-rated primary fuses.<br />

Capacitor banks<br />

Two primary factors affect fuse ratings when used with capacitor banks:<br />

<br />

<br />

the peak inrush current which flows when a capacitor bank is energised. This can be up to 100 times the<br />

nominal current rating of the capacitor bank.<br />

transient voltages produced during capacitor bank switching.<br />

Individual 3-phase capacitor bank<br />

I n (FUSE) = 2 x I_ CAP<br />

U n (FUSE) = 2 x U_ CAP<br />

Back-to-back 3-phase capacitor bank<br />

I n (FUSE) = 3 x I_ CAP<br />

U n (FUSE) = 2 x U_ CAP<br />

Exercise<br />

Select the protection fuse required for a 300 kVAr/7.2 kV individual 3-phase capacitor bank.<br />

I_ CAP<br />

n(FUSE)<br />

I_ CAP<br />

n(FUSE)<br />

U_ CAP<br />

Use 50 A/17.5 kV, general purpose fuses<br />

710-12280-00A <strong>Medium</strong> <strong>Voltage</strong> <strong>Application</strong> <strong>Guide</strong> Page 107