13513.A<br />

SOFT STARTERS<br />

Switchgear Requirements<br />

MVS Panel Options<br />

The MVS soft starter is suitable for operating voltages between 2.3 kV ~ 7.2 kV and currents 600 A, and can be<br />

supplied in switchgear panels.<br />

In all MVS panel options, the following LV equipment is standard and is mounted on the LV compartment door:<br />

<br />

<br />

<br />

E3 panel<br />

Controller<br />

emergency stop pushbutton<br />

soft starter reset pushbutton<br />

E3 panel schematic (for use with MV motor 2.3 kV~7.2 kV, 80 A ~ 600 A)<br />

Q1<br />

F1-3<br />

A1 Soft starter power assembly<br />

Q1 Incoming isolator/earth switch<br />

F1-3 R-rated line fuses<br />

K1 Main contactor<br />

K2 Bypass contactor<br />

K1<br />

A1<br />

K2<br />

3<br />

M<br />

E2 panel<br />

E2 panel schematic (for use with MV motor 2.3 kV~7.2 kV, 80 A ~ 600 A)<br />

A1 Soft starter power assembly<br />

K1 Main contactor<br />

K2 Bypass contactor<br />

3<br />

Short-circuit line protection is provided externally using R-rated fuses or an MV circuit breaker.<br />

710-12280-00A <strong>Medium</strong> <strong>Voltage</strong> <strong>Application</strong> <strong>Guide</strong> Page 45