Incomer feeder<br />

panel<br />

Transformer<br />

Motor<br />

Power factor<br />

bank<br />

SWITCHGEAR<br />

ANSI protection codes<br />

The American National Standards Institute developed a standardised table of numerical codes indicating specific<br />

protection functions. These codes are internationally recognised, and are often used in single line diagrams or<br />

tender documents as part of a project specification.<br />

ANSI codes commonly specified for medium voltage feeders, transformers, motor and power factor banks.<br />

ANSI<br />

code<br />

Function Description <strong>Application</strong> Components<br />

required<br />

CT VT<br />

24 Volts per hertz<br />

relay<br />

25 Synchronising or<br />

synch-check<br />

device<br />

26 Apparatus<br />

device<br />

27 Undervoltage<br />

relay<br />

37 Undercurrent/<br />

power relay<br />

38 Bearing<br />

protective<br />

device<br />

46 Phase reversal or<br />

current<br />

imbalance relay<br />

47 Phase sequence<br />

voltage relay<br />

48 Incomplete<br />

sequence relay<br />

49<br />

(P,R)<br />

50<br />

(N,G)<br />

51<br />

(N,G)<br />

Machine or<br />

transformer<br />

thermal relay<br />

AC<br />

instantaneous or<br />

di/dt relay<br />

AC<br />

time-overcurren<br />

t relay<br />

59 Overvoltage<br />

relay<br />

64 Ground (earth)<br />

detector relay<br />

Activates if the Volts/Hertz ratio falls<br />

outside a preset range.<br />

Operates when the voltage, frequency,<br />

and phase angles between two AC<br />

systems are within a preset acceptable<br />

range.<br />

Activates if the monitored apparatus<br />

exceeds a preset temperature.<br />

Activates if the voltage falls below a preset<br />

level.<br />

Activates if the current or power falls<br />

below a preset level.<br />

Activates when the upper temperature<br />

limit of a machine bearing is exceeded or<br />

abnormal bearing wear is detected.<br />

Monitors line currents and activates when<br />

phase reversal is detected or when line<br />

current imbalance of negative phase<br />

sequence currents fall outside a preset<br />

range.<br />

Monitors line voltages and activates when<br />

phase reversal is detected.<br />

Trips or turns off a device if a particular<br />

sequence has not been completed within<br />

a preset time period.<br />

Activates if the monitored machine or<br />

transformer part exceeds a preset<br />

temperature.<br />

(P = PTC, R = RTD)<br />

Activates if the current or di/dt values<br />

exceed a preset level. Normally indicates a<br />

medium to high level fault condition.<br />

(N = neutral, G = ground)<br />

Activates when the current exceeds a<br />

preset level based on a thermal overload<br />

trip curve.<br />

(N = neutral, G = ground)<br />

Activates if the voltage exceeds a preset<br />

level.<br />

Activates when earth current flow is<br />

detected from the frame, chassis, case or<br />

structure of a device, indicating a<br />

breakdown of insulation in an electrical<br />

machine or transformer.<br />

X<br />

X<br />

X<br />

X<br />

X X X<br />

X X X X<br />

X X<br />

X<br />

X X X<br />

X<br />

X<br />

X<br />

X X X<br />

X X X X X<br />

X X X X X<br />

X X X X<br />

X X X<br />

710-12280-00A <strong>Medium</strong> <strong>Voltage</strong> <strong>Application</strong> <strong>Guide</strong> Page 125