SWITCHGEAR<br />

Single line diagram<br />

Description<br />

Withdrawable circuit breaker The withdrawable circuit breaker provides load switching, short<br />

circuit protection and circuit isolation when opened and in the<br />

draw-out position.<br />

The cable-side earth switch is interlocked with the circuit breaker<br />

and can only be closed when the circuit breaker is in the drawn-out<br />

position.<br />

A protection device is required to provide overload and short circuit<br />

protection.<br />

Withdrawable contactor The withdrawable contactor with integrated fuses provides load<br />

switching and circuit isolation when opened and in the draw-out<br />

position. The fuses provide short circuit protection.<br />

The cable-side earth switch is interlocked with the contactor and<br />

can only be closed when the contactor is in the drawn-out position.<br />

Gas insulated rotary disconnector The gas insulated rotary disconnector has three physical operating<br />

positions. It provides load switching in the ON position, isolation in<br />

the OFF position and earthing in the EARTH position.<br />

Short circuit protection is provided by fuses, but a fixed type circuit<br />

breaker could be used instead.<br />