SWITCHGEAR<br />

NEMA/IEEE Ratings<br />

These ratings are typically used for current transformers manufactured or used in North American installations. As<br />

well as a stated primary to secondary nominal current ratio, the device also carries an overall accuracy rating in the<br />

format<br />

Accuracy class<br />

AC-CR-BU<br />

Where:<br />

AC = accuracy class<br />

CR = class rating<br />

BU = maximum burden (ohms)<br />

Designates the accuracy of the secondary current with respect to the primary rated current. This accuracy is only<br />

guaranteed provided the maximum burden is not exceeded.<br />

Class rating<br />

Accuracy class Tolerance at 100% primary current<br />

1.2 ±1.2%<br />

0.6 ±0.6%<br />

0.5 ±0.5%<br />

0.3 ±0.3%<br />

Designates the intended application of the device.<br />

B =<br />

for metering applications<br />

H = for protection applications. The CT secondary accuracy is guaranteed at 5 to 20 times the nominal<br />

primary rated current<br />

Burden<br />

The maximum load allowed to be connected to the current transformer secondary, to guarantee the accuracy class.<br />

The maximum burden includes secondary cable/wire, connectors and the load. The following table converts burden<br />

in ohms to VA, for a 5 A secondary.<br />

0.04 0.06 0.08 0.12 0.16 0.20 0.24 0.28 0.32 0.36 0.40 0.48 0.56 0.64 0.72 0.80<br />

VA 1 1.5 2 3 4 5 6 7 8 9 10 12 14 16 18 20<br />

Examples<br />

0.5-B-0.1 indicates a current transformer with an accuracy of ±0.5%, and a maximum allowable secondary burden of<br />

0.1 (or 2.5 VA on a 5 A secondary CT). This is a metering class rated current transformer.<br />

1.2-H-0.2 indicates a current transformer with an accuracy of ±1.2%, and a maximum allowable secondary burden<br />

of 0.2 (or 5 VA on a 5 A secondary CT). This is a protection class rated current transformer.<br />

Page 118 <strong>Medium</strong> <strong>Voltage</strong> <strong>Application</strong> <strong>Guide</strong> 710-12280-00A