ELECTRICAL SUPPLY<br />

4. All current transformers (C.Ts) shall be of the epoxy- resin encapsulated type and shall conform<br />

to the requirements of IEC 60044-1, for the type of duty required.<br />

5. The CT’s shall be installed on the side of the circuit breaker remote from the busbars. The<br />

primary winding shall be of the bar type and of approved cross-section compatible with the circuit<br />

breaker rating.<br />

6. The secondary windings of each set of C.Ts shall be earthed at one point.<br />

7. C.Ts. for protective purposes shall be of the nominated protection Class, rated burden and<br />

saturation factor sufficient to cater for the normal relay settings and load burdens required in the<br />

protection scheme.<br />

8. Current transformers used for metering and indicating instruments shall have accuracy not less<br />

than the nominated; typically Class 0.5 and Class 1.0 respectively. Each transformer shall be<br />

capable of providing the necessary VA to operate the related instruments.<br />

3.12 Labels<br />

1. Each item of equipment shall carry the manufacturer's rating plates, with information and<br />

compliance with the relevant standard.<br />

2. Further labelling shall be provided to indicate the main functions of each service and control<br />

equipment item.<br />

3. All wiring terminal positions and terminations shall be identified by local labels to indicate the<br />

group services, e.g. closing, tripping, etc. This shall be in addition to the cable ferrule method.<br />

3.13 Control Wiring<br />

1. Suitably rated terminal blocks shall be provided for all external cable connections.<br />

2. Terminals for circuits carrying different voltages shall be segregated, labelled and separated with<br />

insulating barriers.<br />

3. Control cabling inside electrical panels shall be with PVC V105 insulated stranded single-core<br />

copper cable. The minimum cross section shall be suitable for the load current and volt-drop for<br />

CT secondary wiring or small power circuits.<br />

4. For other control circuits, the minimum size shall be 1.0 mm sq. Wiring shall be neatly run and<br />

shall be securely fixed in insulated ducting or harnesses with easy access for checking.<br />

5. A suitable control wiring colour schedule shall be provided to differentiate voltages and functions.<br />

8