SWITCHGEAR<br />

Exercise<br />

A 17.5 kV secondary distribution, indoor switchgear system requires MO arrestors to be fitted on the incomer side.<br />

The system supply is 15 kV/50 Hz and is isolated from earth. Use calculated ratings and the manufacturers’ data<br />

sheet for selection.<br />

The highlighted numbers 1~4 refer to the solution page.<br />

Step 1: Calculate the MO arrestor ratings<br />

<br />

<br />

<br />

Continuous operating voltage<br />

For an isolated earthed neutral system, continuous operating voltage (U c ) ≥ system voltage (U s )<br />

U c ≥ 15 kV<br />

Rated voltage<br />

Rated voltage (U r ) ≥ 1.25 times continuous operating voltage (U c )<br />

U r ≥ 1.25 x 15<br />

U r ≥ 18.75 kV<br />

Nominal discharge current<br />

For a secondary distribution system, use a lightning-impulse nominal discharge current rating (I n ) of 10 kA.<br />

<br />

Residual protection voltage<br />

The residual protection voltage (U res ) developed across the MO arrester, when discharging 10 kA, must be<br />

less than 70% of the equipment lightning-impulse rating (U p )<br />

U res U p x 0.7<br />

95 x 0.7<br />

66 kV<br />

Step 2: Using the calculated ratings, select an MO arrestor from the manufacturer's data sheet<br />