Percentage DC component<br />

SWITCHGEAR<br />

Rated peak withstand current (kA)<br />

This is the maximum peak fault current level which the device is able to close (make) on. This rating must be<br />

greater than the expected peak let-through fault current (I p ) at the point of installation.<br />

Rated peak withstand current ≥ I p<br />

I p = 2.5 x I s (for a 50 Hz supply with a<br />

45 ms DC time constant)<br />

I p = 2.6 x I s (for a 60 Hz supply with a<br />

45 ms DC time constant)<br />

Source: IEC 62271-1, IEC 62771-100<br />

Rated short circuit breaking capacity, Isc (kA)<br />

Where:<br />

I p = asymmetrical peak let-through fault current, from the first fault<br />

loop (kA)<br />

I s = rms symmetrical fault current level, with no DC component<br />

(kA)<br />

This is the highest level of rms current which the circuit breaker can successfully open (break) on a fault, at its rated<br />

voltage. When a short circuit occurs in a 3-phase system, the initial fault current is asymmetrical and is made up of<br />

an AC symmetrical component and a decaying DC component. The rated short circuit breaking capacity must be<br />

greater than the expected asymmetrical fault current level when the circuit breaker poles are opened.<br />

Where:<br />

I I sc = rated short circuit breaking capacity of circuit breaker (kA)<br />

SC I a<br />

I a = asymmetrical fault current level when circuit breaker poles are<br />

Ia<br />

= Is<br />

+ Id<br />

I s<br />

opened (kA)<br />

= AC symmetrical fault current component (kA)<br />

I d = DC fault current component (kA)<br />

Standard values for I sc = 6.3, 8, 10, 12.5, 16, 20, 25, 31.5, 40, 50, 63 kA (source: IEC 62271-100)<br />

Percentage DC component in fault current<br />

100<br />

90<br />

4 = 120 ms<br />

80<br />

3 = 75 ms<br />

70<br />

2 = 60 ms<br />

60<br />

50<br />

40<br />

30<br />

20<br />

10<br />

1 = 45 ms<br />

0<br />

0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90<br />

Time interval from initiation of short circuit current (ms)<br />

The graph illustrates the percentage DC component of a fault, over a period of time, for systems with various time<br />

constants. Most systems use the standard time constant ( 1 ) of 45 ms. The total opening time of the circuit<br />

breaker is the pole opening time plus 10 ms for relay sensing, and this figure can be used to determine the<br />

percentage DC component of a fault at the instant of breaking.<br />