Percentage DC component<br />
SWITCHGEAR<br />
Rated peak withstand current (kA)<br />
This is the maximum peak fault current level which the device is able to close (make) on. This rating must be<br />
greater than the expected peak let-through fault current (I p ) at the point of installation.<br />
Rated peak withstand current ≥ I p<br />
I p = 2.5 x I s (for a 50 Hz supply with a<br />
45 ms DC time constant)<br />
I p = 2.6 x I s (for a 60 Hz supply with a<br />
45 ms DC time constant)<br />
Source: IEC 62271-1, IEC 62771-100<br />
Rated short circuit breaking capacity, Isc (kA)<br />
Where:<br />
I p = asymmetrical peak let-through fault current, from the first fault<br />
loop (kA)<br />
I s = rms symmetrical fault current level, with no DC component<br />
(kA)<br />
This is the highest level of rms current which the circuit breaker can successfully open (break) on a fault, at its rated<br />
voltage. When a short circuit occurs in a 3-phase system, the initial fault current is asymmetrical and is made up of<br />
an AC symmetrical component and a decaying DC component. The rated short circuit breaking capacity must be<br />
greater than the expected asymmetrical fault current level when the circuit breaker poles are opened.<br />
Where:<br />
I I sc = rated short circuit breaking capacity of circuit breaker (kA)<br />
SC I a<br />
I a = asymmetrical fault current level when circuit breaker poles are<br />
Ia<br />
= Is<br />
+ Id<br />
I s<br />
opened (kA)<br />
= AC symmetrical fault current component (kA)<br />
I d = DC fault current component (kA)<br />
Standard values for I sc = 6.3, 8, 10, 12.5, 16, 20, 25, 31.5, 40, 50, 63 kA (source: IEC 62271-100)<br />
Percentage DC component in fault current<br />
100<br />
90<br />
4 = 120 ms<br />
80<br />
3 = 75 ms<br />
70<br />
2 = 60 ms<br />
60<br />
50<br />
40<br />
30<br />
20<br />
10<br />
1 = 45 ms<br />
0<br />
0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90<br />
Time interval from initiation of short circuit current (ms)<br />
The graph illustrates the percentage DC component of a fault, over a period of time, for systems with various time<br />
constants. Most systems use the standard time constant ( 1 ) of 45 ms. The total opening time of the circuit<br />
breaker is the pole opening time plus 10 ms for relay sensing, and this figure can be used to determine the<br />
percentage DC component of a fault at the instant of breaking.<br />