13809.A<br />

SWITCHGEAR<br />

Calculations: fixed capacitor bank for individual motor<br />

To calculate the fixed capacitor bank power (Q) required to improve the power factor of an individual motor:<br />

U = 6.6 kV<br />

Q (kVAr)<br />

1<br />

M<br />

Q<br />

2<br />

P (kW)<br />

P = 1500 kW<br />

= 0.96<br />

pf 1 = 0.88 (initial power factor)<br />

pf 2 = 0.95 (target power factor)<br />

Q = (tan 1 tan 2 )<br />

Where:<br />

Q = capacitor bank power (kVAr)<br />

P = motor shaft power (kW)<br />

= motor efficiency at full load<br />

1 = phase angle of motor power factor at full load (=cos -1 x pf 1 )<br />

2 = phase angle of target power factor at full load (=cos -1 x pf 2 )<br />

Required power is 325 kVAr<br />

Calculations: PFC capacitor bank<br />

To calculate the capacitor value (C) and nominal current value (I nom ) for a power factor correction capacitor bank:<br />

Capacitance<br />

Where:<br />

C = capacitance (µF)<br />

U 2 (2 f)<br />

Q = capacitor bank power (kVAr)<br />

U = supply voltage (kV)<br />

f = supply frequency (Hz)<br />

<br />

Nominal current<br />

710-12280-00A <strong>Medium</strong> <strong>Voltage</strong> <strong>Application</strong> <strong>Guide</strong> Page 137