SOFT STARTERS<br />

Example<br />

Calculate the acceleration time of a 2000 kW motor driving a pump load from 40% to 50% full speed. The full<br />

load speed is 2990 rpm. Average acceleration torque from 40% to 50% full speed is 20% motor FLT. The motor<br />

shaft inertia is 60 kg·m 2 and the pump inertia is 12 kg·m 2 .<br />

Total inertia is motor plus load inertia:<br />

J T = 60 + 12kgm 2<br />

= 72 kgm 2<br />

Speed difference is 10% of full load speed:<br />

n = n2 n1 × full load speed<br />

= 50% 40% × 2990 rpm<br />

= 299 rpm<br />

Average acceleration torque is 20% of motor FLT.<br />

kW × 9550<br />

FLT =<br />

n<br />

2000 × 9550<br />

=<br />

2990<br />

= 6388 Nm<br />

T av = 6388×<br />

20<br />

100<br />

= 1278 Nm<br />

Calculate the acceleration time from 40% to 50% full load speed:<br />

JT<br />

× n<br />

t acel =<br />

9.55 × T<br />

av<br />

72kgm<br />

=<br />

2 × 299 rpm<br />

9.55 × 1278 Nm<br />

21528<br />

=<br />

12205<br />

= 1.76 sec<br />

Page 58 <strong>Medium</strong> <strong>Voltage</strong> <strong>Application</strong> <strong>Guide</strong> 710-12280-00A