Incomer feeder<br />

panel<br />

Transformer<br />

Motor<br />

Power factor<br />

bank<br />

SWITCHGEAR<br />

ANSI<br />

code<br />

Function Description <strong>Application</strong> Components<br />

required<br />

CT VT<br />

67 AC directional<br />

current relay<br />

79 AC reclosing<br />

relay<br />

Activates when the current, flowing in a<br />

specific direction, exceeds a preset level.<br />

This protection is based on 50 and 51<br />

functions.<br />

Controls the automatic reclosing and<br />

locking-out of an AC circuit switching<br />

device.<br />

81 Frequency relay Activates if the frequency falls outside a<br />

preset range.<br />

86 Locking-out Shuts down or holds equipment out of<br />

relay<br />

service under abnormal conditions. May<br />

be manually or electrically operated.<br />

87 (L,<br />

T, M)<br />

Differential<br />

protection relay<br />

Activates if the detected current on<br />

opposite sides of a machine or<br />

transformer are not equal to each other.<br />

(L = line, T = transformer,<br />

G = generator)<br />

X<br />

X<br />

X<br />

X<br />

X X X X<br />

X X X<br />

AuCom soft starter ANSI protection functions<br />

The following ANSI code protections are standard in AuCom medium voltage soft starters. For details of additional<br />

protections in MVS and MVX which are not listed in this table, refer to the relevant user manual.<br />

ANSI ANSI Function<br />

MVS/MVX Trip<br />

Code<br />

26 Apparatus device Motor thermal model<br />

27/59 Under/overvoltage relay Undervoltage and overvoltage<br />

37 Undercurrent/power relay Undercurrent<br />

46 Phase reversal or current imbalance relay Phase sequence and current imbalance<br />

48 Incomplete sequence relay Excess start time<br />

50 AC instantaneous or di/dt relay Instantaneous overcurrent<br />

51 AC time-overcurrent relay Time-overcurrent<br />

64 Ground (earth) detector relay Ground fault<br />

81 Frequency relay Supply frequency<br />

Temperature related protection functions such as motor winding and bearing protection require a separate<br />

protection device which can be installed in the LV section of the soft starter panel.<br />

Page 126 <strong>Medium</strong> <strong>Voltage</strong> <strong>Application</strong> <strong>Guide</strong> 710-12280-00A