SWITCHGEAR<br />

4.10 Protection index<br />

IP Ratings<br />

IEC 60529 specifies levels of protection against the ingress of different items. Ingress protection (IP) codes are<br />

composed of up to four elements:<br />

<br />

<br />

<br />

<br />

Characteristic 1: Solid foreign objects<br />

Characteristic 2: Harmful ingress of liquid<br />

Additional letter (optional): Object used for access<br />

Supplementary letter (optional): <strong>Application</strong> specific<br />

IP rating components<br />

Characteristic 1 Characteristic 2 Additional Letter Supplementary Letter<br />

0 Non-protected Non-protected A = back of hand H = high voltage apparatus<br />

1 ≥ 50 mm diameter Vertically dripping B = finger M = motion during water test<br />

2 ≥ 12.5 mm diameter Dripping at 15 ° tilt C = tool S = stationary during water test<br />

3 ≥ 2.5 mm diameter Spraying D = wire W = weather conditions<br />

4 ≥ 1.0 mm diameter Splashing<br />

5 Dust-protected Jetting<br />

6 Dust-tight Powerful jet<br />

7 Temporary immersion<br />

8 Continuous immersion<br />

Source: IEC 60529<br />

IEC 62271-1 specifies protection ratings for enclosures. Equipment designed for indoor installation is not typically<br />

IP rated against ingress of water (a placeholder X is used instead of a rating for this characteristic):<br />

IP ratings for equipment installed indoors<br />

Degree of Protection against ingress of solid foreign Protection against access to hazardous parts<br />

Protection<br />

objects<br />

IP1XB Protected against solid objects greater than 50<br />

mm<br />

Access with a finger (test-finger 12 mm<br />

diameter, 80 mm length)<br />

IP2X Protected against solid objects greater than 12.5<br />

mm<br />

Access with a finger (test-finger 12 mm<br />

diameter, 80 mm length)<br />

IP2XC Protected against solid objects greater than 12.5<br />

mm<br />

Access with a tool (test rod 2.5 mm diameter,<br />

100 mm length)<br />

IP2XD Protected against solid objects greater than 12.5<br />

mm<br />

Access with a wire (test wire 1.0 mm diameter,<br />

100 mm length)<br />

IP3XC Protected against solid objects greater than 2.5<br />

mm<br />

Access with a tool (test rod 2.5 mm diameter,<br />

100 mm length)<br />

IP3XD Protected against solid objects greater than 2.5<br />

mm<br />

Access with a wire (test wire 1.0 mm diameter,<br />

100 mm length)<br />

IP4X Protected against solid objects greater than 1<br />

mm<br />

Access with a wire (test wire 1.0 mm diameter,<br />

100 mm length)<br />

IP5X Protection against harmful entry of dust Access with a wire (test wire 1.0 mm diameter,<br />

100 mm length)<br />

Source: IEC 62271-1<br />

Page 170 <strong>Medium</strong> <strong>Voltage</strong> <strong>Application</strong> <strong>Guide</strong> 710-12280-00A