Medium Voltage Application Guide
Medium Voltage Application Guide
Medium Voltage Application Guide
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
SWITCHGEAR<br />
CPT selection - Inrush VA at selected voltage drop<br />
Inrush VA<br />
Nominal VA rating<br />
85% voltage drop 90% voltage drop 95% voltage drop<br />
347 289 216 63<br />
338 290 229 80<br />
907 745 541 130<br />
1267 1039 754 200<br />
1394 1116 781 250<br />
2870 2298 1584 350<br />
3786 3013 2065 500<br />
7360 5763 3786 750<br />
7360 5763 3786 800<br />
8837 6785 4329 1000<br />
14921 11328 7070 1600<br />
20500 14850 9100 2000<br />
CPT selection - power factor adjustment factor<br />
Power factor 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0<br />
Adjustment factor 1.5 1.29 1.11 1.00 0.91 0.82 0.78 0.71 0.67 0.64<br />
Exercise<br />
A transformer with its primary connected to 7.2 kV, has a 110 VAC secondary with a total inrush loading of<br />
850 VA and a resistive load of 100 VA. The total sealed VA of the load is 200 VA.<br />
A voltage drop of 85% is acceptable during the inrush stage. The power factor of the inrush current is 0.3.<br />
Calculate the necessary power rating of the control supply power transformer.<br />
1. The total inrush loading is 950 VA (850 VA + 100 VA). The next highest Inrush VA figure in the 85% volt<br />
drop column is 1267 VA.<br />
2. An Inrush VA of 1267 VA equates to a Nominal VA rating of 200 VA.<br />
3. 200 VA seems acceptable as this is equivalent to the total sealed load VA.<br />
4. The inrush current has a power factor of 0.3. Using the power factor adjustment factor, the transformer has<br />
a revised Nominal VA rating of 222 VA (200 x 1.11). The next highest standard size would be 250 VA.<br />
Use a 7.2 kV/110 VAC, 250 VA single phase control supply power transformer.<br />
Transformer primary fuses must withstand the inrush magnetising current which flows when a<br />
transformer primary is switched on. With a medium voltage primary, E-rated fuses are used and often<br />
selected to withstand 25 times the nominal primary current for 0.01 second and 12 times the nominal<br />
primary current for 0.1 second.<br />
710-12280-00A <strong>Medium</strong> <strong>Voltage</strong> <strong>Application</strong> <strong>Guide</strong> Page 129