SWITCHGEAR<br />

4.2 Standard Enclosure Configurations<br />

Incomer Feeder Panel (IFP)<br />

As the name implies, this panel configuration serves two purposes:<br />

As an incomer panel. This switches the incoming main supply onto the common horizontal busbar system<br />

of a metal-enclosed switchgear arrangement<br />

As a feeder panel. This switches the main supply from the common horizontal busbar system of a<br />

metal-enclosed switchgear arrangement onto a specific feeder circuit.<br />

The enclosure will always have a main circuit breaker (normally withdrawable), housed in its own compartment of<br />

the panel. An earth switch at the cable termination end of the circuit provides isolation during shutdown and<br />

maintenance. Interlocking ensures that the earth switch cannot be closed until the main circuit breaker is open and<br />

racked-out into the test position. Current transformers are fitted to interface with a protection relay for circuit<br />

breaker trip operation.<br />

Depending on the required function, voltage transformers can be supplied. These can be 3-phase or single phase,<br />

either fixed or withdrawable style. A variety of low voltage equipment is used, which is mounted in its own<br />

segregated compartment, situated at the top-front of the enclosure assembly.<br />

AuCom provides an Incomer Feeder Panel as part of its L-Series switchgear range. This is rated at 12 kV<br />

from 630 A to 2000 A. An IAC classification of 31.5 kA for 1 second is achieved by double skin<br />

compartments, special locking door designs and top-exit arc flaps for pressure release.<br />

Incomer Feeder Panel (IFP)<br />

Typical Incomer Feeder Panel<br />

Front view Side view Rear view<br />

1<br />

2<br />

1 Circuit breaker (withdrawable)<br />

2 Current transformer set<br />

3 Earth switch<br />

4 <strong>Voltage</strong> transformer (fused and<br />

withdrawable)<br />

3<br />

4<br />