11165.A<br />
11163.A<br />
SWITCHGEAR<br />
4.2 Standard Enclosure Configurations<br />
Incomer Feeder Panel (IFP)<br />
As the name implies, this panel configuration serves two purposes:<br />
As an incomer panel. This switches the incoming main supply onto the common horizontal busbar system<br />
of a metal-enclosed switchgear arrangement<br />
As a feeder panel. This switches the main supply from the common horizontal busbar system of a<br />
metal-enclosed switchgear arrangement onto a specific feeder circuit.<br />
The enclosure will always have a main circuit breaker (normally withdrawable), housed in its own compartment of<br />
the panel. An earth switch at the cable termination end of the circuit provides isolation during shutdown and<br />
maintenance. Interlocking ensures that the earth switch cannot be closed until the main circuit breaker is open and<br />
racked-out into the test position. Current transformers are fitted to interface with a protection relay for circuit<br />
breaker trip operation.<br />
Depending on the required function, voltage transformers can be supplied. These can be 3-phase or single phase,<br />
either fixed or withdrawable style. A variety of low voltage equipment is used, which is mounted in its own<br />
segregated compartment, situated at the top-front of the enclosure assembly.<br />
AuCom provides an Incomer Feeder Panel as part of its L-Series switchgear range. This is rated at 12 kV<br />
from 630 A to 2000 A. An IAC classification of 31.5 kA for 1 second is achieved by double skin<br />
compartments, special locking door designs and top-exit arc flaps for pressure release.<br />
Incomer Feeder Panel (IFP)<br />
Typical Incomer Feeder Panel<br />
Front view Side view Rear view<br />
1<br />
2<br />
1 Circuit breaker (withdrawable)<br />
2 Current transformer set<br />
3 Earth switch<br />
4 <strong>Voltage</strong> transformer (fused and<br />
withdrawable)<br />
3<br />
4<br />
Page 74 <strong>Medium</strong> <strong>Voltage</strong> <strong>Application</strong> <strong>Guide</strong> 710-12280-00A