Medium Voltage Application Guide
Medium Voltage Application Guide
Medium Voltage Application Guide
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
14043.A<br />
14042.A<br />
SCHEMATIC DIAGRAMS<br />
5.3 Contactor Control (Typical)<br />
<strong>Medium</strong> voltage contactors have two methods of control.<br />
<br />
<br />
single command operated control (SCO) - this requires a permanent signal to close and maintain the<br />
contactor in the closed position. Removal of the control signal will open the contactor.<br />
double command operated control (DCO) - this requires two separate momentary contacts; one for the<br />
close command and one for the open command. The DCO control method typically uses normally open,<br />
spring return pushbuttons for both the open and close commands.<br />
Typically, command signals require an external voltage source and the contactor controller itself requires a separate<br />
auxiliary voltage source. Depending on the contactor make and model, electrical options are available. Some<br />
examples are:<br />
Undervoltage shunt trip<br />
Lock-out solenoid<br />
Racking solenoid<br />
Auxiliary contacts<br />
Racking contacts<br />
Fuse blow indicator contacts<br />
only used with DCO control<br />
needs to be externally energised before contactor main poles can be electrically<br />
operated<br />
needs to be externally energised before a withdrawable contactor can be moved<br />
between the test and service positions<br />
indicate the electrical state of the main contactor poles<br />
indicate whether a withdrawable contactor is in the service or test position<br />
indicate fuse condition. - operated by striker pin and only available on contactors<br />
with integral medium voltage fuses<br />
The following examples show typical contactor control circuits:<br />
Single command operated contactor control (typical)<br />
Auxiliary supply<br />
KA1<br />
3<br />
Contactor controller<br />
Control signal (maintained)<br />
1<br />
4<br />
2<br />
A<br />
B<br />
External trip contact (eg from MPR)<br />
Control supply<br />
Control input<br />
A<br />
B<br />
Double command operated contactor control (typical)<br />
1<br />
A B C<br />
3<br />
2<br />
A<br />
B<br />
C<br />
Auxiliary supply<br />
Contactor controller<br />
External trip contact (eg from MPR)<br />
Control supply<br />
Close input<br />
Open input<br />
Page 174 <strong>Medium</strong> <strong>Voltage</strong> <strong>Application</strong> <strong>Guide</strong> 710-12280-00A