Maximum cut-off current (kA, peak)<br />
SWITCHGEAR<br />
Example<br />
A fuse with a nominal rating of 50 A has a minimum break current of 200 A and is capable of passing an overload<br />
current of 240 A for 10 seconds.<br />
Let-through curves<br />
Sometimes referred to as cut-off curves, they indicate the ability of a fuse to limit the peak let-through and rms values<br />
of short circuit current, immediately downstream of the fuse installation.<br />
Sample fuse let-through curves<br />
100<br />
10<br />
200<br />
160<br />
125<br />
100<br />
80<br />
63<br />
50<br />
40<br />
31.5<br />
25<br />
20<br />
16<br />
10<br />
6<br />
1<br />
0.1<br />
0.01 0.1 1 10 Jp 100<br />
Prospective current (kA, rms)<br />
Source: example curves based on ABB CEF fuse links<br />
Example<br />
If the prospective rms fault current was 5 kA, the peak let-through current would be approximately 12 kA without<br />
a fuse. If a 50 A fuse was installed, the rms fault current would be limited to 1.5 kA and the peak let-through current<br />
would be 3.8 kA downstream of the fuse.<br />
I 2 t data<br />
Fuse data sheets provide two I 2 t figures:<br />
minimum I 2 t is the amount of let-through energy required to start a fuse melt and create an arc<br />
maximum I 2 t is the total amount of let-through energy required to extinguish an arc and completely<br />
rupture (open circuit) a fuse.<br />
This data is important for fuse discrimination. The maximum I 2 t of the downstream fuse must be less than the<br />
minimum I 2 t of the upstream fuse.<br />
If a fuse is selected to protect a cable, the maximum I 2 t of the fuse must be greater than the A 2 S 2 thermal rating of<br />
the cable.<br />
Ratings<br />
Irrespective of which standard a fuse has been type tested too, the following generic ratings usually apply. Different<br />
standards require different rating information to be published on the fuse nameplate.<br />