SWITCHGEAR<br />

Overcurrent protection based on measuring the 3-phase line currents, produces positive sequence current (I 1 ,<br />

indicative of phase-to-phase faults) or negative phase sequence current (I 2 , indicative of phase loss or phase<br />

imbalance). Overcurrent protection based on measuring the residual or ground current, produces zero sequence<br />

current (I 0 , indicative of ground fault or earth leakage).<br />

The configuration of the CTs depends on the functionality of the protection device:<br />

Line current protection<br />

L1 L2 L3<br />

Line current and residual current protection<br />

L1 L2 L3<br />

I_A<br />

I_A<br />

I_B<br />

I_B<br />

I_C<br />

I_C<br />

Io<br />

Positive sequence current, I 1<br />

Negative sequence current, I 2<br />

Ground current protection<br />

Positive sequence current, I 1<br />

Negative sequence current, I 2<br />

Zero sequence current, I 0<br />

Ground current protection<br />

HV<br />

TXR<br />

Zero sequence current, I 0<br />

1<br />

MV<br />

Io<br />

Zero sequence current, I 0<br />

Page 122 <strong>Medium</strong> <strong>Voltage</strong> <strong>Application</strong> <strong>Guide</strong> 710-12280-00A