SCHEMATIC DIAGRAMS<br />

5.4 Automatic Changeover Systems<br />

In medium voltage distribution networks, it is important to maintain a high level of reliability. Industry relies on the<br />

continuous operation of critical plant, which requires no or little disruption to the electrical supply. There are<br />

various methods for building redundancy of supply into a system. The most commonly used methods are a dual<br />

transformer fed supply and/or a standby generator sized to keep critical plant online.<br />

Automatic changeover systems are designed to monitor and maintain continuous supply. Today's technology<br />

allows the supervision and control of an entire distribution system from a single controller, referred to as an<br />

automatic transfer switch (ATS) or automatic changeover unit (ACU). Although there are a wide range of<br />

products available, they all have the same primary function.<br />

The equipment monitors 3-phase voltages on all power sources. Power supply sources are often prioritised and if<br />

any phase voltage on the primary power source falls outside a predetermined range for a specific amount of time,<br />

the power source is switched over to a back-up supply. Once the primary power source is re-established, the<br />

power source is switched back to the primary power source. In medium voltage systems, switching is performed<br />

using either contactors or circuit breakers. Most ATS controllers can control both types of switching devices.<br />

Automatic changeover systems range from simple main/standby set-ups to highly complex distribution systems and<br />

this is where the selection of an appropriate ATS controller is important. Systems can be operated in automatic or<br />

manual mode.<br />

<br />

<br />

In AUTO mode, supervision and power source switching is carried out entirely by the ATS controller.<br />

In MANUAL mode, power source switching is carried out by manual selection via the ATS controller.<br />

NOTE<br />

For safety reasons, manual mode cannot be used in certain network configurations.<br />

Overview<br />

The following are examples of common operating modes in automatic changeover systems. Most ATS controllers<br />

can be programmed to operate in any one of these modes.<br />

N1+N2<br />

N1<br />

N2<br />

K1<br />

K2<br />

AUTO mode with line priority:<br />

N1 is the prioritised power source and, if healthy, will always supply the receiving network (DB). If N1 is lost, the<br />

controller switches over to power source N2. The controller switches back to N1 once it has been re-established.<br />

AUTO mode without line priority:<br />

The first power source verified as healthy will supply the receiving network (DB). If this power source is lost, the<br />

other power source will be selected and remain as the supply as long as it is healthy. If both power sources are lost,<br />

both sources N1 and N2 are isolated from the receiving network (DB)<br />

MANUAL mode:<br />

DB<br />

Select N1 or N2 as the power source<br />

710-12280-00A <strong>Medium</strong> <strong>Voltage</strong> <strong>Application</strong> <strong>Guide</strong> Page 175