Motor Line Inductors on Soft Starter <strong>Application</strong>s<br />

Long motor cables on the output of a soft starter are seen as a capacitive load which creates a di/dt current transient<br />

at each SCR turn-on event. If the current transient repeatedly exceeds the di/dt rating of the SCR, failure will occur.<br />

Soft starter start current waveform<br />

1500<br />

1000<br />

500<br />

0<br />

-500<br />

300<br />

200<br />

100<br />

0<br />

63.05 63.10<br />

-1000<br />

-1500<br />

55 59 63 67 71<br />

The current transient, peak value and rate-of-rise are are installation dependent, and are determined by many factors<br />

external to the soft starter. The di/dt value of the current transient is proportional to the system voltage (for<br />

example, the value for a 6.6 kV system will be approximately twice as much as a 3.3 kV system).<br />

At a critical cable length, the cable capacitance must be negated by line inductance to avoid damaging current<br />

transients. Air-core line inductors are specified according to the installation and are fitted close to the soft starter<br />

output terminals.<br />

4<br />

5<br />

1<br />

2<br />

M<br />

3<br />

3<br />

13768.A<br />

3-phase supply<br />

Soft starter<br />

Line inductors<br />

Cable capacitance<br />

MV motor<br />

Soft starter SCRs are most vulnerable to current transient damage at two stages of the motor starting procedure:<br />

<br />

<br />

in the initial ramp-up to the start current (current limit) level.<br />

when the SCRs reach full conduction and just before the motor current falls to the running current level.<br />

The latter stage is potentially more damaging. AuCom medium voltage soft starters are bypassed in run state and<br />

the SCRs are turned off, minimising the risk of current transient damage.<br />

Current transient influences<br />

The di/dt current transients that occur at SCR turn-on are influenced by the following factors:<br />

<br />

<br />

<br />

<br />

<br />

<br />

System voltage and frequency<br />

Total cable capacitance upstream and downstream of the soft starter<br />

Motor characteristics (kW, efficiency, starting power factor)<br />

Soft starter snubber component values (RC network components)<br />

Control stage of the motor start-up period<br />

Start current (current limit) level<br />

Page 130 <strong>Medium</strong> <strong>Voltage</strong> <strong>Application</strong> <strong>Guide</strong> 710-12280-00A