ENVIRONMENTAL SPECIFICATIONS<br />
Environmental Specifications<br />
2.1 Environmental Specifications<br />
2.2 Physical Specifications<br />
The equipment shall be suitable for storage at temperatures from -25 ºC to +55 ºC.<br />
The equipment shall be suitable for use at temperatures from -10 ºC to +60 ºC.<br />
The equipment shall be suitable for use at temperatures up to 40 ºC without<br />
derating.<br />
The equipment shall be suitable for operation at altitudes up to 1000 m above sea<br />
level without derating.<br />
The equipment shall be suitable for use in environments with relative humidity<br />
between 5% and 95% (non-condensing).<br />
The equipment shall be modular in design and construction.<br />
The power factor correction components must be installed in a dedicated panel<br />
and not the soft starter panel.<br />
The integrated power factor panel must be enclosed up to IP4X and include:<br />
• Withdrawable Vacuum, fused contactor with ratings:<br />
1. Class: indoor withdrawable<br />
2. Rated <strong>Voltage</strong>: 12 kV<br />
3. Rated lightning impulse withstand voltage: 75 kV (peak)<br />
4. Rated 1-minute power frequency withstand voltage: 28 kV (rms)<br />
5. Rated Frequency: 50 Hz<br />
6. Rated short circuit breaking current: 20 kA (with fuses)<br />
7. Rated short circuit making current: 62.5 kA (with fuses)<br />
8. Duty: continuous<br />
9. Utilisation factor: AC6<br />
10. Protection coordination: Type 2<br />
11. Minimum Service Life: 100,000 operations at full operating current.<br />
• Inrush reactors designed to reduce the inrush current to that required by<br />
IEC60871-1. The supplier must provide calculations for the correct selection of<br />
the reactors.<br />
• Capacitors shall be selected to improve the power factor to the level required<br />
by the local utility.<br />
• The capacitor shall have a voltage rating 20% above the nominal operating<br />
voltage so as to be able to withstand high voltages associated with capacitor<br />
switching.<br />
• The capacitor circuit must be supplied from the line side of the soft starter.<br />
• All panels must provide separate chambers for all main sections including<br />
Busbars, Contactor, Capacitors. The entire panel, including inter-chamber,<br />
must be arc fault certified to 31.5kA for 3 seconds.<br />
• All panels shall have the following ratings:<br />
1. IAC classified AFLR<br />
2. Rated short term withstand current: 31.5kA for 3 seconds<br />
3. BIL: 75kV<br />