2.<br />

ENVIRONMENTAL SPECIFICATIONS<br />

Environmental Specifications<br />

2.1 Environmental Specifications<br />

2.2 Physical Specifications<br />

The equipment shall be suitable for storage at temperatures from -25 ºC to +55 ºC.<br />

The equipment shall be suitable for use at temperatures from -10 ºC to +60 ºC.<br />

The equipment shall be suitable for use at temperatures up to 40 ºC without<br />

derating.<br />

The equipment shall be suitable for operation at altitudes up to 1000 m above sea<br />

level without derating.<br />

The equipment shall be suitable for use in environments with relative humidity<br />

between 5% and 95% (non-condensing).<br />

The equipment shall be modular in design and construction.<br />

The thyristor assembly for each phase shall consist of a discrete module, and be<br />

individually replaceable<br />

Replacement of a thyristor assembly by a qualified service technician shall not take<br />

longer than 10 minutes.<br />

The integrated starter must be enclosed up to IP4X and include:<br />

• Withdrawable Vacuum, fused Line contactor with ratings:<br />

• Fixed Vacuum Bypass contactor<br />

All contactors shall have the following ratings:<br />

1. Class: indoor withdrawable<br />

2. Rated <strong>Voltage</strong>: 12 kV<br />

3. Rated lightning impulse withstand voltage: 75 kV (peak)<br />

4. Rated 1-minute power frequency withstand voltage: 28 kV (rms)<br />

5. Rated Frequency: 50 Hz/60 Hz<br />

6. Rated short circuit breaking current: 20 kA (with fuses)<br />

7. Rated short circuit making current: 62.5 kA (with fuses)<br />

8. Duty: continuous<br />

9. Utilisation factor: AC3<br />

10. Protection coordination: Type 2<br />

11. Minimum Service Life: 100,000 operations at full operating current.<br />

• A pad-lockable earthing switch<br />

• All panels must provide separate chambers for all main sections including Bus<br />

bars, Line Contactor, Soft starters and LV control. The entire panel, including<br />

inter-chamber, must be arc fault certified to 31.5kA for 1 seconds.<br />

• All panels shall have the following ratings:<br />

1. IAC classified AFLR<br />

2. Rated short term withstand current: 31.5 kA for 3 seconds<br />

3. BIL: 75 kV<br />

• The equipment shall employ fibre-optic cabling to ensure complete isolation<br />

between low voltage and high voltage circuitry.<br />