3.<br />

ELECTRICAL SUPPLY<br />

Electrical Supply<br />

3.1 General<br />

The main power supply to the plant shall be from the power supply authority at XXkV<br />

All equipment provided under this Contract shall be suitable for continuous operation at the voltage<br />

and conditions noted below. Compliance is required to clause 9.101 of IEC 62271-200; “Information<br />

with enquiries and orders”<br />

All equipment and work associated with the Contract shall be entirely suitable for operation on the<br />

plant power supply systems as specified; and tabled below<br />

Nominal voltage between phases<br />

xxkV<br />

Number of Phases 3<br />

System fundamental frequency<br />

TBA Hz<br />

System Neutral<br />

TBA<br />

Design Fault Level<br />

xx kA for xx sec<br />

Loss of Service Continuity Category<br />

TBA<br />

Internal Arc Classification<br />

TBA<br />

3.2 Standards<br />

The work, equipment and other items shall comply with the requirements of relevant IEC and other<br />

nominated standards, codes and regulations; including those referenced throughout the<br />

Specification and any other Authorities having jurisdiction over any portion of the work, and on the<br />

method of performing such work.<br />

Where there is any discrepancy between the referenced standards and this Specification (and<br />

associated Contract Drawings), the requirements of this Specification (and associated Contract<br />

Drawings) shall have precedence.<br />

3.2.1 Switchgear<br />

Designed to:<br />

a) Switchgear and apparatus IEC62271-1<br />

IEC62271-200<br />

IEC62271-304<br />

GB3906 (2006)<br />

DL-T-404<br />

DL-T-593<br />

b) Internal arc resistance IEC62271-200<br />

Annex A.6, criteria 1 to 5<br />

c) Levels of insulation (coordination guide) IEC60071<br />

d) Degrees of protection IEC60529<br />

e) Seismic The Uniform Building code,<br />

Section 1629.6.8<br />

IEC60721-2-6, Table 1 for static<br />

load test<br />

f) Drilled holes and screw connections for busbars DIN43673-1<br />

g) Classification of groups of environmental parameters<br />

and their severities – Storage<br />

IEC60721-3-1<br />

h) Classification of groups of environmental parameters<br />

and their severities – Transportation<br />

i) Classification of groups of environmental parameters<br />

and their severities –<br />

Stationary use at weather protected locations<br />

IEC60721-3-2<br />

IEC60068-2-32<br />

IEC60721-3-3<br />

4