Assessed Start Current Estimate<br />

SOFT STARTERS<br />

If information is available about the intended motor's locked rotor current (LRC) and locked rotor torque (LRT), the<br />

motor's start performance can also be factored into the assessment. Even better estimates are obtained where<br />

information on the machine start torque requirement are also known.<br />

Required information:<br />

<br />

<br />

<br />

<br />

Motor size (kW / HP)<br />

Motor locked rotor current (LRC)<br />

Motor locked rotor torque (LRT)<br />

Machine starting torque (% FLT)<br />

Calculation<br />

Calculations use percentages of full load torque and full load current.<br />

Minimum required start current<br />

I<br />

STR<br />

= LRC ×<br />

TSTR<br />

LRT<br />

Where:<br />

I STR = minimum required start current (% motor FLC)<br />

LRC = Motor locked rotor current (% motor FLC)<br />

T STR = Minimum required start torque to accelerate machine from<br />

standstill (% motor FLT)<br />

LRT = Motor locked rotor torque (% motor FLT)<br />

Example<br />

A 1100 kW / 3.3 kV motor has a full load current of 235 A and a locked rotor current of 500% FLC. The motor<br />

is required to start a pump with a minimum start current of 15% motor FLT. The motor's locked rotor torque is<br />

150% FLT.<br />

I STR = 500% FLC ×<br />

= 500 × 0.316<br />

= 158% FLC<br />

158<br />

= ×<br />

100 235 A<br />

= 371 A<br />

15%FLT<br />

150%FLT<br />

Start Current and Torque Curve Analysis<br />

To accurately calculate an application's start current requirements, torque and current curves for both the motor<br />

and the load are required. Information from these curves is used to assess the minimum start current requirements.<br />

With the following information, specific application software can accurately estimate the minimum required start<br />

current (I STR ) and start time (t STR ):<br />

<br />

<br />

<br />

<br />

<br />

Motor datasheet (including kW, full load speed and motor shaft inertia)<br />

Motor speed/current curve<br />

Motor speed/torque curve<br />

Load speed/torque curve<br />

Load inertia<br />