Medium Voltage Application Guide
Medium Voltage Application Guide
Medium Voltage Application Guide
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Assessed Start Current Estimate<br />
SOFT STARTERS<br />
If information is available about the intended motor's locked rotor current (LRC) and locked rotor torque (LRT), the<br />
motor's start performance can also be factored into the assessment. Even better estimates are obtained where<br />
information on the machine start torque requirement are also known.<br />
Required information:<br />
<br />
<br />
<br />
<br />
Motor size (kW / HP)<br />
Motor locked rotor current (LRC)<br />
Motor locked rotor torque (LRT)<br />
Machine starting torque (% FLT)<br />
Calculation<br />
Calculations use percentages of full load torque and full load current.<br />
Minimum required start current<br />
I<br />
STR<br />
= LRC ×<br />
TSTR<br />
LRT<br />
Where:<br />
I STR = minimum required start current (% motor FLC)<br />
LRC = Motor locked rotor current (% motor FLC)<br />
T STR = Minimum required start torque to accelerate machine from<br />
standstill (% motor FLT)<br />
LRT = Motor locked rotor torque (% motor FLT)<br />
Example<br />
A 1100 kW / 3.3 kV motor has a full load current of 235 A and a locked rotor current of 500% FLC. The motor<br />
is required to start a pump with a minimum start current of 15% motor FLT. The motor's locked rotor torque is<br />
150% FLT.<br />
I STR = 500% FLC ×<br />
= 500 × 0.316<br />
= 158% FLC<br />
158<br />
= ×<br />
100 235 A<br />
= 371 A<br />
15%FLT<br />
150%FLT<br />
Start Current and Torque Curve Analysis<br />
To accurately calculate an application's start current requirements, torque and current curves for both the motor<br />
and the load are required. Information from these curves is used to assess the minimum start current requirements.<br />
With the following information, specific application software can accurately estimate the minimum required start<br />
current (I STR ) and start time (t STR ):<br />
<br />
<br />
<br />
<br />
<br />
Motor datasheet (including kW, full load speed and motor shaft inertia)<br />
Motor speed/current curve<br />
Motor speed/torque curve<br />
Load speed/torque curve<br />
Load inertia<br />
710-12280-00A <strong>Medium</strong> <strong>Voltage</strong> <strong>Application</strong> <strong>Guide</strong> Page 55