Mechanical Properties<br />

Compressive strength of the concrete was measured using standard cylinders,<br />

6" diameter × 12" long, following the method of ASTM C 39. <strong>The</strong><br />

compressive strength of concrete Mixture CON-C is shown in Table 4-53. <strong>The</strong><br />

compressive strength of the mixture was very low at the early age and could<br />

not be measured until the age of 16 days. At the age of 16 days, the<br />

compressive strength was only 60 psi. <strong>The</strong> compressive strength increased at<br />

the age of 28 days to 135 days, and then significantly increased at the 42-day<br />

age to 1345 psi. This indicates that the setting time of the concrete mixture<br />

was significantly delayed, as well as pozzolanic effect of 40% fly ash content<br />

contributing to this jump in strength. <strong>The</strong> delay in setting was attributed to the<br />

amount of high-range water reducing admixture (HRWRA) required to be<br />

added to the mixture. <strong>The</strong> amount of HRWRA exceeded the maximum<br />

amount recommended by the manufacturer (136 oz/yd 3 versus 170 oz/yd 3<br />

actually used in the laboratory mixture). Another possibility investigated was<br />

to determine if the water-soluble sizing of the carbon fibers had any effect on<br />

the setting time of the mixtures. <strong>The</strong> water-soluble sizing is applied to prevent<br />

the agglomeration of the fibers.<br />

A test was conducted on cement mortar cubes per ASTM C 109 using water<br />

that was obtained from soaking the carbon fibers for 24 hours. <strong>The</strong><br />

compressive strength of the cement mortar cubes at the age of seven days was<br />

5070 psi. This indicates that the water-soluble sizing probably did not have<br />

any time of setting delay effect on the compressive strength of cement mortar.<br />

<strong>The</strong> concrete compressive strength achieved for the Mixture CON-C tested for<br />

this project is below its normally expected strength level. <strong>The</strong> primary focus<br />

of this project was to determine the effect of carbon fibers on the electrical<br />

properties of the concrete. <strong>The</strong>refore, the compressive strength of the mixtures<br />

was considered secondary at this stage of the study. <strong>The</strong> amount of fibers can<br />

be revised in the future phases to produce a good-quality structural-grade<br />

concrete. <strong>The</strong> amount of carbon fibers may be reduced and optimized for<br />

electrical properties. Compressive strength of the concrete may be increased<br />

by increasing the cementitious materials and/or reducing the amount of water<br />

in the mixture.<br />

<strong>We</strong> <strong>Energies</strong> 126<br />

<strong>Coal</strong> <strong>Combustion</strong> <strong>Products</strong><br />

Utilization Handbook