Table 4-9: Time of Setting*<br />

NON-AIR-ENTRAINED CONCRETE<br />

Mix No.<br />

Nominal<br />

28-day<br />

Compressive<br />

Strength, psi<br />

Nominal<br />

Percentage of<br />

Fly Ash<br />

Time of Setting, HR:MIN<br />

Initial<br />

Final<br />

P4-43 3,000 35 6:55 8:30<br />

P4-24 3,000 45 7:45 9:55<br />

P4-25 3,000 55 8:45 11:20<br />

P4-44 4,000 35 7:35 9:25<br />

P4-26 4,000 45 7:30 9:50<br />

P4-27 4,000 55 7:55 10:25<br />

P4-45 5,000 35 6:30 8:15<br />

P4-28 5,000 45 7:15 9:25<br />

P4-29 5,000 55 7:00 9:15<br />

AIR-ENTRAINED CONCRETE<br />

Mix No.<br />

Nominal<br />

28-day<br />

Compressive<br />

Strength, psi<br />

Nominal<br />

Percentage of<br />

Fly Ash<br />

Time of Setting, HR:MIN<br />

Initial<br />

Final<br />

P4-46 3,000 35 6:40 8:40<br />

P4-47 3,000 45 8:15 10:25<br />

P4-38 3,000 55 7:15 9:45<br />

P4-48 4,000 35 7:30 9:45<br />

P4-39 4,000 45 6:40 9:10<br />

P4-40 4,000 55 6:55 9:30<br />

P4-49 5,000 35 6:45 8:20<br />

P4-41 5,000 45 7:30 9:40<br />

P4-42 5,000 55 5:40 7:10<br />

* Determined in accordance with ASTM Designation: C-403-85 Time of Setting of Concrete<br />

Mixtures by Penetration Resistance<br />

<strong>The</strong> final setting time for 4000 psi and 5000 psi concrete showed much less<br />

increase with increase in fly ash content. <strong>The</strong> 5000 psi concrete with 55% fly<br />

ash content actually showed a decrease by 10 minutes for final setting time<br />

compared to 5000 psi concrete with 45% fly ash content.<br />

<strong>The</strong> initial and final setting time for air-entrained concrete is also shown on<br />

Table 4-9. It can be seen from the results that the initial and final setting time<br />

for air-entrained fly ash concrete is not significantly different as the fly ash<br />

replacement is increased to levels of 55% for the 3,000; 4,000; and 5,000 psi<br />

concrete.<br />

<strong>We</strong> <strong>Energies</strong> 66<br />

<strong>Coal</strong> <strong>Combustion</strong> <strong>Products</strong><br />

Utilization Handbook