Figure E.7: Shielding around the edge <strong>of</strong> an observation window<br />

Lead sheets in contact with lead glass must have an overlap <strong>of</strong> at least 1.5 cm or the thickness <strong>of</strong> the lead<br />

glass, whichever is greater.<br />

Wall <strong>of</strong><br />

concrete<br />

or brick<br />

Lead glass<br />

WHO 40219<br />

102<br />

<strong>The</strong> <strong>Design</strong> <strong>of</strong> <strong>Diagnostic</strong> <strong>Medical</strong> <strong>Facilities</strong> <strong>where</strong> Ionising Radiation is used