30.01.2015 Views

The Design of Diagnostic Medical Facilities where ... - ResearchGate

The Design of Diagnostic Medical Facilities where ... - ResearchGate

The Design of Diagnostic Medical Facilities where ... - ResearchGate

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

5.2.4 Primary radiation<br />

A barrier is required to attenuate the primary beam to a level that complies with the dose constraint. Primary<br />

barriers are typically required in general radiographic rooms, dedicated chest rooms and rooms <strong>where</strong> there<br />

is a combination <strong>of</strong> radiography and fluoroscopy. For mammography, fluoroscopy, CT and DXA – the entire<br />

primary beam is normally incident on the face <strong>of</strong> the image detector which acts as a primary beam stop.<br />

<strong>The</strong>refore for these types <strong>of</strong> rooms only secondary radiation needs to be considered.<br />

<strong>The</strong> use factor (U) is the fraction <strong>of</strong> the primary beam workload that is directed toward a given barrier (NCRP,<br />

2004). It is used in the NCRP methodology for primary radiation shielding calculations and the value will<br />

depend on the type <strong>of</strong> installation and the barrier being assessed. Different barriers may have different use<br />

factors. For example, the workload presented for the radiographic room (Chest Bucky) in Table 5.4 is directed<br />

entirely at the wall behind the Bucky, and the use factor, U = 1 for this wall. In addition, this workload only<br />

contributes secondary radiation to the other barriers in the room. However, it should be noted that a more<br />

complex situation can arise with other configurations.<br />

Primary beam use factors published by the NCRP are reproduced in Table 5.6. <strong>The</strong> ceiling and operator’s<br />

control screen are generally considered to have U = 0. U is also zero for installations <strong>where</strong> only secondary<br />

radiation needs to be considered such as image intensifier and mammography systems.<br />

Table 5.6: Use factors from NCRP for radiographic room (based on NCRP, 2004)<br />

Barrier Use factor (U) Workload distribution<br />

Floor 0.89 Rad Room (floor or other barriers)<br />

Cross-table wall 0.09 Rad Room (floor or other barriers)<br />

Unspecified wall (other than chest<br />

bucky wall or cross-table wall)<br />

0.02 Rad Room (floor or other barriers)<br />

Chest Bucky wall 1.00 Rad Room (Chest Bucky)<br />

To calculate the shielding required in the primary barrier, the barrier transmission factor must be determined.<br />

This is the ratio <strong>of</strong> the air kerma behind a barrier <strong>of</strong> thickness, x, to the air kerma at the same location with<br />

no barrier. In the following sections, an overview <strong>of</strong> the BIR methodology and equations are presented.<br />

Detailed equations for employing the NCRP methodology are available (NCRP, 2004). A comparison <strong>of</strong> both<br />

methods is presented in Example 1 in Section 5.3.<br />

BIR methodology for primary radiation<br />

<strong>The</strong> BIR recommends that one <strong>of</strong> two methods is used to calculate primary shielding requirements, and the<br />

method used will depend on the clinical situation. <strong>The</strong> film dose method is used <strong>where</strong> the X-ray beam is<br />

entirely intercepted by the patient and the entrance surface dose method is used <strong>where</strong> this is not the case.<br />

56<br />

<strong>The</strong> <strong>Design</strong> <strong>of</strong> <strong>Diagnostic</strong> <strong>Medical</strong> <strong>Facilities</strong> <strong>where</strong> Ionising Radiation is used

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!