<strong>hager</strong>"<strong>DALI</strong> <strong>Gateway</strong> C00Cx2" softwareParametersResponse at the end ofthe disable function(continued)Memory value (brightnessprior to the last shutoff)Tracked brightness valueAt the end of the disable, the value will beadjusted to the brightness value that wasactive and internally stored prior to the lastswitch-off (via the “Switching” or “Switchingcentral function” object). This memoryvalue is non-permanently stored so that thevalue is pre-defined to the maximumbrightness after the return of bus voltage orafter programming with the ETS. The busmode of the group will be re-enabledafterwards.Time functions will be included.At the end of a disable, the status receivedor set prior to the executed disable functionwill be resumed with the applicablebrightness value. If applicable, active timefunctions will also be considered.• This parameter becomes visible only ifthe disable function is enabled.Seite 117 von 130