<strong>hager</strong>"<strong>DALI</strong> <strong>Gateway</strong> C00Cx2" softwareObject tableFunction: Staircase timer function 3Object Function Name Type DP type Flag5, 12, 19, … , 110 Staircase timer Group 1 ... 16 1-bit 1.010 C, W, -, (R) 1function start/stopDescription: 1-bit object for activating or deactivating the switching time of the Staircase timerfunction of an output ("1" = on / "0" = off).Function: Disable functionObject Function Name Type DP type FlagDisable Group 1 ... 32 1-bit 1.003 C, W, – (R) 16, 13, 20, … , 111117, 123, …, 207Description:1-bit object for disabling a group (polarity is parameterizable).Function: Forced-control position functionObject Function Name Type DP type Flag6, 13, 20, … , 111 Forced-control Group 1 ... 32 2-bit 2.001 C, W, – (R) 1117, 123, …, 207positionDescription: 2-bit object for the forced-control position of a group. The polarity will be provided bythe telegram.3 The Staircase timer function can only be parameterized for the first 16 groups.1 Each communication object can be read-out. The readout requires the setting of the R flag.Seite 26 von 130