fault relay (132KV&25KV side)<br />

4. IDMT overcurrent relay CDG-16 80-320% Of 5A<br />

(25kv side)<br />

5. Aux relays for buchholz VAA-33<br />

excessive winding and oil<br />

tem tripping<br />

B) OHE PROTECTION<br />

1 MHO type directional YCG-14 0.33 to 12 ohm extended<br />

distance protection zone each upto 60 ohm<br />

relay(DPR) <strong>of</strong> 5A with MTA 75 de<br />

gree<br />

2 MHO relay for protection YCG-14 0.33 to 12 ohm extended<br />

against wrong phase zone reach upto 60 ohm<br />

coupling(WC) <strong>of</strong> 5A with MTA 125 de<br />

gree with forward <strong>of</strong>fset<br />

<strong>of</strong> 11%<br />

3. Instantaneous high set CAG-17 100-800%<strong>of</strong> 5A<br />

over current relay on<br />

25KVside(OC)<br />

C) AUXILIARY RELAYS<br />

1 D.C Supervision<br />

i) Transformer HV CB VAA-11<br />

Trip supervision<br />

ii) Transformer LV CB VAA-11<br />

iii) 25KV Feeder <strong>control</strong> VAA-11<br />

iv) 25KV intrruptor <strong>control</strong> VAA-11<br />

v) 5.DC fail alarm cancel VAA-11<br />

vi) Alarm annunciation VAA-11<br />

<strong>control</strong><br />

SN Discription Type Rating/setting<br />

design range<br />

2. Auxiliary realy for VAA-11<br />

contact multiplication<br />

<strong>of</strong> directiional distance<br />

protection relay(YCG-14)<br />

3. Alarm bell realy VAA-21<br />

4. Flasher relay VAA-21<br />

5. Timer relay for single VAT-11<br />

shot Auto-Reclosing<br />

102