3. Check if the terminations <strong>of</strong> the overhead shield wire covering the<br />

whole sub-station are In good physical condition and properly bonded<br />

electrically to the structures.<br />

4. Check and record resistance <strong>of</strong> each group <strong>of</strong> earth electrodes, after<br />

disconnecting it from common earth system. Improve, K necessary.<br />

5. Check condition <strong>of</strong> connections to the burried rails.<br />

3.9.4 Traction Transformers<br />

3.9.5<br />

1. Send samples to approved laboratory for all tests listed at Annex.<br />

3.03B (IS 1866) including dissolved gas analysis.<br />

2. Check oil level in bushings.<br />

3. Inspect bushing gaskets for leaks and tighten bolts.<br />

4. Move the tap-setting switch up and down the full range a few times so<br />

that by self-wiping action good contact is assured. Set the tap finally at<br />

the correct position making sure that tap-indication corresponds to<br />

position <strong>of</strong> main contacts.<br />

5. Paint transformer tank on such parts as required.<br />

Isolators<br />

1. Smoother burrs, If any on the blade tips and fixed contact fingers with<br />

fine emery paper and smear Vaseline.<br />

2. Measure clearance <strong>of</strong> blade in open position and record and adjust<br />

crank mechanism, if found necessary.<br />

3. Check the adjustable stop set-screws for proper condition and correct<br />

positioning.<br />

4. If the Isolator is motor-operated, measure and record insulation<br />

resistance <strong>of</strong> motor windings and contactor coils using a 500 V<br />

megger.<br />

3.9.6. Bus Bars and Connectors<br />

Measure with a 'Ductor' or other low resistance measuring Instrument the<br />

contact resistances <strong>of</strong> all connections which are carrying heavy currents.<br />