1.1 Schedules<br />

MAINTENANCE OF SF6 CIRCUIT BREAKERS<br />

64<br />

Annexure 3.06<br />

The maintenance and check execution standard depends upon the working<br />

conditions <strong>of</strong> the CB. The checks to be carried out. Their frequency and scope are<br />

broadly as under:<br />

Type <strong>of</strong> check Frequency Scope<br />

Patrol<br />

Inspection<br />

Ordinary<br />

inspection<br />

Detailed<br />

Inspection<br />

Incidental<br />

Inspection<br />

1.2 General<br />

Every week<br />

After every<br />

1000 operations<br />

After every<br />

3000 operations<br />

The patrol inspection is an external check<br />

<strong>of</strong> the circuit breaker in live conditions for<br />

irregularities.<br />

The ordinary inspection is inspection<br />

Performed by turning <strong>of</strong>f the circuit breaker<br />

for a relatively short time for simple<br />

inspection and servicing with emphasis on<br />

functional checks e.g. visual check <strong>of</strong><br />

irregularities and cleaning <strong>of</strong> dust and dirt.<br />

The detailed inspection is an inspection<br />

performed by turning <strong>of</strong>f the circuit breaker<br />

for a relatively long time. To dismantle and<br />

inspect the mechanism for irregularities for<br />

the purpose <strong>of</strong> continuously maintaining the<br />

performance.<br />

____ The incidental inspection is performed<br />

when inspection and repair are necessary<br />

due to the detection <strong>of</strong> an irregularity during<br />

patrol inspection.<br />

Attention should be paid to the following points during ordinary and detailed inspection.<br />

a) Switch <strong>of</strong>f <strong>control</strong>/compressor motor supply. Discharge all the air in the air receiver<br />

through the drain value.<br />

b) The circuit breaker is to be inspected in the open position unless otherwise specified<br />

in these Instructions. At the open position <strong>of</strong> the breaker the safety pins for preventing<br />

closing and opening must be inserted. On completion <strong>of</strong> the safety pins must be removed.<br />

c) Good quality grease should be used adequately.<br />

d) Circlips and split pins which are removed must be replace with new ones.<br />

e) Removed “O” rings must be replaced with new ones. While handling and placing “O”<br />

rings in their grooves. Care should be taken to avoid dust falling on them.