scheme<br />
6. Auxiliary relay for VAA-61<br />
Auto reclosing scheme<br />
7. High speed Master trip VAJH-13<br />
relay<br />
8. High speed inter trip VAJH-13<br />
relay<br />
9. Auxiliary relay for VAA-43<br />
Buchholz oil temp/<br />
winding temp/low oil alarm<br />
10. Alarm annunciation relay VAA-121<br />
5.8 SCHEME OF PROTECTION FOR 132/25 KV OR 110/25 KV OR 66/25 KV TRANS-<br />
FORMER<br />
5.8.1 Differential protection<br />
Protection against internal fault shall be provided by means <strong>of</strong> a senstive single-pole diffrential<br />
relays. The relays shall be <strong>of</strong> the high speed type and shall operate in less than two cycles.The<br />
relays shall incorporate the following feature<br />
i) There shall be no necessity for changing the setting <strong>of</strong> relays when the transformer<br />
tap is changed.The transformer is provided with tap from -15% to +10%.<br />
ii) Necessary harmonic restraining feature shall be incorporated to prevent operation due<br />
to in rush <strong>of</strong> magnetisation current when the transformer is charged either from the<br />
HV or the LV side.<br />
iii) The relays shall not operate for maximum through fault current.<br />
iv) The current setting <strong>of</strong> the relays shall be adjustable, preferably between range <strong>of</strong> 20%<br />
and 80%.The minimum current setting shall be as low as possible to obtain better<br />
senstivity.<br />
v) Adjustable bias setting should also be provided .The bias at minimum operating current<br />
setting shall be 20%,30% or 40% to suit the tapping range <strong>of</strong> the traction transformer<br />
and other designed considerations.<br />
The relays shall be connected to bushing type current transformer provided in the bushings<br />
<strong>of</strong> 132/25 kV,110/25kV transformer.However,interposing current transformers <strong>of</strong> suitable ratio and<br />
ratig with matching charcteristics <strong>of</strong> knee point voltage , excitation current etc. shall be provided<br />
with the diffrentialrelays in order to boost up the bushing CTs secondary current, at full load,<br />
to a value equal to relays rated current.Magnetisation ratio error curves for the crrent transformers<br />
103