REGULATION FOR ELECTRICAL CROSSING OF RAILWAY TRACKS<br />
9.0 Provision <strong>of</strong> the regulation for power line crossing <strong>of</strong> Railway Track, 1987 are<br />
given below.<br />
9.0.1 Power line crossing up to and including 11kv require to be cabled and crossed underground<br />
9.0.2 Power Line Crossings up to and including 33kv is recommended to be croosed<br />
through underground cables.<br />
9.0.3 For overhead crossing <strong>of</strong> power lines, the minimum height above rail level to the<br />
lowest conductor including the guard wire shall be as given below.<br />
Voltage(kv) Minimum height<br />
above Rail level(m)<br />
above 11 to 66 14.10<br />
above 66 to 132 14.60<br />
above 132 to 220 15.40<br />
above 220 to 400 17.90<br />
above 400 to 500 19.30<br />
above 500 to 800 23.40<br />
9.0.4 The angle <strong>of</strong> overhead crossing shall be perpendicular to the track. In exceptional cases<br />
it may be permitted with a skew, the angle <strong>of</strong> deviation not exceeding 30 degree. In case it is<br />
likely to be more than this value the case should be referred to the <strong>Electrical</strong> Inspector to the<br />
government (Chief <strong>Electrical</strong> Engineer <strong>of</strong> the open Line Railway).<br />
9.0.5 In view <strong>of</strong> high cost <strong>of</strong> modifications to Power Line Crossing and also difficulty in getting<br />
shut down <strong>of</strong> important transmission line crossings <strong>of</strong> tracks contemplated to be electrified<br />
<strong>Electrical</strong> inspectors to Government may approve crossings with lower heights provided the<br />
clearance between lowest conductor <strong>of</strong> the power line to the highest traction conductor under<br />
most adverse ambient temperature condition is as indicated below.<br />
Voltage(kv) Minimum clearance(m)<br />
0 to 66 4.44<br />
above 66 to 110 4.75<br />
above 110 to 132 5.05<br />
220 6.58<br />
400 9.71<br />
500 11.45<br />
800 16.67<br />
If power line crossing has guard wire minimum clearance from the guard wire to the highest<br />
traction conductonr should be 2 m<br />
156