vii) Rated short circuit 31.5 kA 20 kA<br />
breaking current<br />
viii) Rated breaking capacity<br />
(Symmetrical)<br />
a) Two Pole 7717.5 MVA 450 MVA<br />
b) Three pole 13366.7 MVA<br />
ix) Rated making current 78.8 kA 50 kA<br />
x) Rated operating sequence 0-0.3 sec 0-0.3 sec<br />
83<br />
CO-3 sec. - CO 30 sec -CO<br />
xi) Total breaking time Not more than 80 ms. Not more than 65 ms<br />
xii) Rated short time 31.5 kA for 20 kA for<br />
withstand current one second 3 seconds<br />
4.5 25 KV INTERRUPTORS<br />
4.5.1 The interruptors ar non-automatic circuit breakers which are provided at feeding<br />
posts and switching stations. Inter rupters ar not required to clear the fault, except for the<br />
one which is provided at the sectioning post as bridging interruptor. This interruptor is called<br />
upon to clear the fault under extended feed conditions. The breaking capacity <strong>of</strong> the<br />
interruptor has been specified as 4000 Amps at a recovery voltage <strong>of</strong> 27.5 kV and a short<br />
time current with stand capacity <strong>of</strong> 4000 Amps. for 3 seconds. But now with the use <strong>of</strong><br />
higher rating traction transformers, the breaking capacity and normal rated current has been<br />
incrased to 8 kA and 800 Amps respectively in the RDSO’s new specification.<br />
4.6 ISOLATING SWITCHES<br />
4.6.1 When carrying, out inspection or repair on sub-station <strong>equipment</strong>s, it is<br />
essential to disconnect reliably the unit or the section, on which the work is to be done,<br />
from all other live parts on the installation in order to ensure complete safety <strong>of</strong> the working staff<br />
to guard against mistakes, it is desirable that this should be done by an apparatus which<br />
makes a visible break in the circuit. Such an apparatus is called the isolating switch or isolator.<br />
Isolators are used to open or close the circuit either when negligible current is flowing or when<br />
no current is flowing through the circuit. These are also called as <strong>of</strong>f load switches. The location<br />
<strong>of</strong> the isolating switch is decided in the sub-station on the basis <strong>of</strong> scheme <strong>of</strong> bus bar<br />
connections. Generally on either side <strong>of</strong> the circuit breakers, isolators are provided for<br />
attending to maintenance work etc.<br />
4.6.2 Two types <strong>of</strong> isolating switches have been used in traction substation. On the<br />
primary side i.e. HV side. Isolators used are either <strong>of</strong> two pole or three pole according to<br />
number <strong>of</strong> poles. From constructional point <strong>of</strong> view these may be divided as.