3.8.4 Control and Relay Panels<br />
1. Check tightness <strong>of</strong> all connections, remove cobwebs and wipe <strong>of</strong>f<br />
accumulated dust with dry cloth.<br />
2. Check if tap and time settings <strong>of</strong> the relays ate in order.<br />
3. Examine fuses for signs <strong>of</strong> overheating or aging, springiness and<br />
cleanliness <strong>of</strong> contact making parts. Clean up and lightly Vaseline to<br />
ensure proper contact. ,<br />
3.9. YEARLY MAINTENANCE<br />
3.9.1 General<br />
1. Inspect the fence all-round the sub-station and bending between metal<br />
fencing panels and to earth. Put a drop <strong>of</strong> oil in the hinges <strong>of</strong> all doors.<br />
Repaint any <strong>of</strong> the structural parts as necessary.<br />
2. Open all the trench rover and clean them completely. Clean all culverts<br />
and remove cobwebs: check possibility <strong>of</strong> lizards or other insects<br />
gaining entry into enclosed <strong>control</strong> <strong>equipment</strong>, and make them insectpro<strong>of</strong>.<br />
3. Arrange for painting <strong>of</strong> walls and metal-works as necessary.<br />
4. Check all explosion vent diaphragms for any damage.<br />
5. Check rod gap setting.<br />
3.9.2 Lightning Arresters<br />
1. Check earthing terminals and earth strips for proper condition. Check<br />
connection to the line.<br />
2. Where lightning arrestors are provided with discharge counters, record<br />
the counter reading.<br />
3.9.3 Bonding and Earthing<br />
1. Check physically the soundness <strong>of</strong> bonding and earthing connections<br />
lo every electrical <strong>equipment</strong> structural steel, lightning arrester etc. and<br />
inter-panel connections.<br />
2. Record earth resistance to body <strong>of</strong> electrical <strong>equipment</strong> as well as to all<br />
parts <strong>of</strong> the fencing and structural steel work.<br />