3.8.4 Control and Relay Panels<br />

1. Check tightness <strong>of</strong> all connections, remove cobwebs and wipe <strong>of</strong>f<br />

accumulated dust with dry cloth.<br />

2. Check if tap and time settings <strong>of</strong> the relays ate in order.<br />

3. Examine fuses for signs <strong>of</strong> overheating or aging, springiness and<br />

cleanliness <strong>of</strong> contact making parts. Clean up and lightly Vaseline to<br />

ensure proper contact. ,<br />

3.9. YEARLY MAINTENANCE<br />

3.9.1 General<br />

1. Inspect the fence all-round the sub-station and bending between metal<br />

fencing panels and to earth. Put a drop <strong>of</strong> oil in the hinges <strong>of</strong> all doors.<br />

Repaint any <strong>of</strong> the structural parts as necessary.<br />

2. Open all the trench rover and clean them completely. Clean all culverts<br />

and remove cobwebs: check possibility <strong>of</strong> lizards or other insects<br />

gaining entry into enclosed <strong>control</strong> <strong>equipment</strong>, and make them insectpro<strong>of</strong>.<br />

3. Arrange for painting <strong>of</strong> walls and metal-works as necessary.<br />

4. Check all explosion vent diaphragms for any damage.<br />

5. Check rod gap setting.<br />

3.9.2 Lightning Arresters<br />

1. Check earthing terminals and earth strips for proper condition. Check<br />

connection to the line.<br />

2. Where lightning arrestors are provided with discharge counters, record<br />

the counter reading.<br />

3.9.3 Bonding and Earthing<br />

1. Check physically the soundness <strong>of</strong> bonding and earthing connections<br />

lo every electrical <strong>equipment</strong> structural steel, lightning arrester etc. and<br />

inter-panel connections.<br />

2. Record earth resistance to body <strong>of</strong> electrical <strong>equipment</strong> as well as to all<br />

parts <strong>of</strong> the fencing and structural steel work.<br />