3.9.7 Control and Relay Panels<br />

1 . Carry out maintenance on relays as detailed in para 3.3.7<br />

2. Check and dean up <strong>control</strong> switches and push-button contacts for burnt<br />

or corroded marks; polish the surfaces. Check also if the contact<br />

springs have the correct springiness.<br />

3.9.8. Batteries and Battery Chargers<br />

If the battery is not in a healthy condition or if there is excessive accumulation<br />

<strong>of</strong> sediment, the whole battery should be replaced with a new set.<br />

Battery Charger<br />

Open out the covers <strong>of</strong> the battery charge and blowout all dust. Check<br />

tightness <strong>of</strong> all connections, bolts, nuts and screws. Measure and record the<br />

insulation resistance <strong>of</strong> the transformer windings <strong>of</strong> the batten,' charger with 500 V<br />

megger.<br />

3.9.9. PTs and CTs<br />

1. Test oil samples if possible.<br />

2. Check rod gap setting, if provided.<br />

3. Measure insulation resistance.<br />

4. Check conditions <strong>of</strong> fuses <strong>of</strong> PTs and terminal connections for CTs.<br />

3.9.10. Special maintenance Schedule for SF6 Circuit Breakers and<br />

Interrupters<br />

Before staring maintenance <strong>of</strong> any switchgears ensure that the instruction<br />

manual <strong>of</strong> the <strong>equipment</strong> issued by the manufacturer have been fully studied and full<br />

knowledge <strong>of</strong> the working <strong>of</strong> switchgears is available with the maintenance<br />

personnel. Otherwise there may be adverse effect on the performance <strong>of</strong><br />

switchgears and it may also endanger the safety <strong>of</strong> working personnel.<br />

The periodicity <strong>of</strong> maintenance is:<br />

i) Fortnightly<br />

ii) Quarterly<br />

iii) Annually<br />

iv) Three yearly<br />

v) Eight yearly<br />

vi) Ten yearly<br />