INCASE OF TWO TRANSFORMERS RUNNING IN PARALLEL -<br />

TOTAL REACTANCE = 1% + 30% = 31%<br />

FAULT LEVEL =<br />

FAULT CURRENT =<br />

100 X 100<br />

31<br />

322.58<br />

25<br />

= 322.58 MVA 60%<br />

= 12.90 KA.<br />

It will be seen from the above that though the fault current is less but rated short circuit<br />

braking current value assigned to the breaker is higher. This is because IEC, IS and BS<br />

specification have standardised the rated short circuit breaking current are as given below :-<br />

6.0 kA, 8.0 kA, 12.5 kA, 16 kA, 20 kA, 25 kA, 31.5 kA, 40 kA, 50 kA, 63 kA, 80kA,<br />

and 100 kA.<br />

Therefore, as a part <strong>of</strong> standardisation, the recommeded values <strong>of</strong> rated short circuit<br />

breaking current have been adopted Recommended values <strong>of</strong> rated short circuit current and<br />

normal rated current are shown as under :-<br />

CO-ORDINATION TABLE OF RATED VALUES FOR CIRCUIT BREAKERS<br />

Rated Rated Short Rated Normal Current<br />

Voltage circuit Breaking (Amps)<br />

(kV) Current (kA)<br />

12.5 800 1250<br />

16 800 1250<br />

72.5 20 1250 1600 2000<br />

31.5 1250 1600 2000<br />

12.5 800 1250<br />

20 1250 1600 2000<br />

123 25 1250 1600 2000<br />

40 1600 2000<br />

12.5 800 1250<br />

20 1250 1600 2000<br />

145 25 1250 1600 2000<br />

31.5 1250 1600 2000<br />

40 1600 2000<br />

50 2000<br />

81<br />

3 1%<br />

3 3<br />

220 KV BUS<br />

60%<br />

25 KV BUS