1.0 General<br />

Annexure 3.05<br />

MAINTENACE OF VACUUM CIRCUIT BREAKERS<br />

The maintenance and check execution standard depends upon the working<br />

conditions <strong>of</strong> VCB. Such as the environmental condition. Current switching<br />

frequency and others. The checks to be carried out. Their frequency and cope are<br />

broadly as under:<br />

Type <strong>of</strong> check Frequency Scope<br />

Patrol Check Daily Check VCB under daily<br />

Ordinary check Once every 3<br />

Year or once every 1000<br />

switching times<br />

Detailed check Every 6 years “<br />

Provisional check When a trouble occurs. “<br />

68<br />

operating condition<br />

Check VCB after<br />

disconnection main supply<br />

and local Remote switch in<br />

LOCAL position.<br />

For the minimum number <strong>of</strong> operation without replacement <strong>of</strong> vacuum bottle Para<br />

1.5 below may be referred.<br />

1.1 Patrol Check<br />

Patrol check shall be done visually. If any abnormality is found, stop the operation<br />

forthwith and examine.<br />

Item No. Check Items Checking parts & key points. Explanation<br />

1. General parts a) Dust and moisture<br />

condensation and evidence<br />

<strong>of</strong> rain water in operating<br />

box.<br />

b) Unusal sound, small and<br />

decolouration.<br />

c) Condition <strong>of</strong> open-close<br />

indication<br />

d) Working condition <strong>of</strong><br />

charge indicator<br />

2. Temperature Main circuit terminals and<br />

electrode pole assembly<br />

3. Control<br />

voltage<br />

Check if the operating<br />

voltage and <strong>control</strong> voltage<br />

are kept at the respective<br />

specified values.<br />

“On in red. closed<br />

condition. “<strong>of</strong>f’ in<br />

green open<br />

condition<br />

Check carefully if the<br />

terminal section is<br />

discoloured and<br />

also, the air is<br />

waving with heat.