1.5 Detailed Check<br />
Checking shall be performed as per items in ordinary check and as per items listed<br />
below:<br />
Item Classificat Checking& Recommended Checking & Remarks<br />
No. ion Servicing Servicing procedure<br />
Standard<br />
checking<br />
intervals.<br />
1. VI Vacuum check Contract manufacture 6 years<br />
3000<br />
operations.<br />
2. Operating<br />
units<br />
3. Check <strong>of</strong><br />
operating<br />
condition<br />
Operating<br />
mechanism<br />
Check <strong>of</strong><br />
adjusting<br />
dimensions <strong>of</strong><br />
each part<br />
Lubrication to rotary part,<br />
sliding parts and pin engaging<br />
part (use low viscosity<br />
machine oil or equivalent.)<br />
Gap between trip hook and<br />
roller followers and other<br />
adjusting dimensions Refer to<br />
clause 5-6<br />
Spring Rust, damage and<br />
deformation<br />
70<br />
6 years<br />
6 years<br />
6 years<br />
Coils Breaking <strong>of</strong> wires and others. 6 years<br />
Min. Operating<br />
voltage<br />
Tripping voltage:<br />
Under 70% rated voltage<br />
Closing Voltage : under 85%<br />
rated voltage<br />
6 years