(d) High speed inter tripping relay. In the event <strong>of</strong> failure <strong>of</strong> traction sub-station, 25 KV<br />

supply is extended from the adjacent sub-station by closing the bridging interruptor<br />

at sectoining post Under such emergency feed conditons, wrong phase coupling<br />

may be caused at the overlap oppostite the failed S. S. by the pantograph <strong>of</strong> the<br />

locomotive, rasulting in the tripping <strong>of</strong> 25 KV CB at any one <strong>of</strong> two S/S through<br />

wrong phase coupling relay (Mho). This may result in the formation <strong>of</strong> an arc at<br />

the overlap due to which the OHE may be damaged. The damage due to arc can<br />

be minimised by tripping the feeder circuit breaker at the other sub-station also.<br />

This is achieved by an inter tripping arrangement through the <strong>remote</strong> <strong>control</strong><br />

<strong>equipment</strong>.<br />

(e) Auto reclosing <strong>of</strong> feeder circuit breakers single shot auto-reclosing scheme for 25 KV<br />

feeder circuit breakers at the traction sub-station has been adopted to facilitate<br />

reclosing <strong>of</strong> the 25 KV feeder circuit breaker authomatically once after a preset<br />

time delay after tripping <strong>of</strong> the circuit breaker on OHE fault. This feature will help<br />

in quick restoration <strong>of</strong> traction power supply to OHE if the fault is <strong>of</strong> transient<br />

nature. It will also help in checking the continuance <strong>of</strong> arc in the event <strong>of</strong> the<br />

pantograph <strong>of</strong> a moving locomotive passing the overlap opposite the feeding post.<br />

(f) Panto Flash Over protection relay : Panto Flash Over relay is provided for<br />

protection <strong>of</strong> OHE from flash over at insulated over lap in front <strong>of</strong> Traction sub -<br />

station, when pantograph passes from live OHE to dead OHE across the over lap.<br />

This relay opens the closed feeder circuit breaker to prevent melting down <strong>of</strong><br />

OHE. Relay can be bypassed either locally or Remotely. One relay monitors one<br />

Line.<br />

Principle and Operation :<br />

When ever one <strong>of</strong> section <strong>of</strong> insulating over-lap (IOL) is tripped on intermittent fault,<br />

and electric train enters from live to dead section <strong>of</strong> the FP-IOL, there shall be a<br />

heavy flash over, particularly when the Panto leaves the IOL which may damage the<br />

Panto. The extent <strong>of</strong> damage is dependent upon the intensity <strong>of</strong> current drawn by<br />

locomitive. to indentify such situtation and trip the feeder circuit breaker connected to<br />

the live side <strong>of</strong> the overlap.<br />

Refer Fig. PFRS the single line diagram <strong>of</strong> typical traction substration (TSS). One<br />

side <strong>of</strong> the insulated overlap, A or B can become dead while other section is live<br />

due to the tripping <strong>of</strong> respective feeder CB on fault or manual tripping. This<br />