(d) High speed inter tripping relay. In the event <strong>of</strong> failure <strong>of</strong> traction sub-station, 25 KV<br />
supply is extended from the adjacent sub-station by closing the bridging interruptor<br />
at sectoining post Under such emergency feed conditons, wrong phase coupling<br />
may be caused at the overlap oppostite the failed S. S. by the pantograph <strong>of</strong> the<br />
locomotive, rasulting in the tripping <strong>of</strong> 25 KV CB at any one <strong>of</strong> two S/S through<br />
wrong phase coupling relay (Mho). This may result in the formation <strong>of</strong> an arc at<br />
the overlap due to which the OHE may be damaged. The damage due to arc can<br />
be minimised by tripping the feeder circuit breaker at the other sub-station also.<br />
This is achieved by an inter tripping arrangement through the <strong>remote</strong> <strong>control</strong><br />
<strong>equipment</strong>.<br />
(e) Auto reclosing <strong>of</strong> feeder circuit breakers single shot auto-reclosing scheme for 25 KV<br />
feeder circuit breakers at the traction sub-station has been adopted to facilitate<br />
reclosing <strong>of</strong> the 25 KV feeder circuit breaker authomatically once after a preset<br />
time delay after tripping <strong>of</strong> the circuit breaker on OHE fault. This feature will help<br />
in quick restoration <strong>of</strong> traction power supply to OHE if the fault is <strong>of</strong> transient<br />
nature. It will also help in checking the continuance <strong>of</strong> arc in the event <strong>of</strong> the<br />
pantograph <strong>of</strong> a moving locomotive passing the overlap opposite the feeding post.<br />
(f) Panto Flash Over protection relay : Panto Flash Over relay is provided for<br />
protection <strong>of</strong> OHE from flash over at insulated over lap in front <strong>of</strong> Traction sub -<br />
station, when pantograph passes from live OHE to dead OHE across the over lap.<br />
This relay opens the closed feeder circuit breaker to prevent melting down <strong>of</strong><br />
OHE. Relay can be bypassed either locally or Remotely. One relay monitors one<br />
Line.<br />
Principle and Operation :<br />
When ever one <strong>of</strong> section <strong>of</strong> insulating over-lap (IOL) is tripped on intermittent fault,<br />
and electric train enters from live to dead section <strong>of</strong> the FP-IOL, there shall be a<br />
heavy flash over, particularly when the Panto leaves the IOL which may damage the<br />
Panto. The extent <strong>of</strong> damage is dependent upon the intensity <strong>of</strong> current drawn by<br />
locomitive. to indentify such situtation and trip the feeder circuit breaker connected to<br />
the live side <strong>of</strong> the overlap.<br />
Refer Fig. PFRS the single line diagram <strong>of</strong> typical traction substration (TSS). One<br />
side <strong>of</strong> the insulated overlap, A or B can become dead while other section is live<br />
due to the tripping <strong>of</strong> respective feeder CB on fault or manual tripping. This<br />
92