B. Insulation resistance will continue to remain at a low level despite<br />

temperature being maintained at a high level until most <strong>of</strong> the moisture<br />

from the windings and oil has been driven out.<br />

C. The insulation resistance will thereafter rise gradually and level <strong>of</strong>f,<br />

indicating that all moisture has been driven out and the drying out<br />

operation has been completed. At this point oil circulation should be<br />

discontinued.<br />

D. As the oil cools <strong>of</strong>f, the insulation resistance will rise above the leveling<br />

<strong>of</strong>f point at the end <strong>of</strong> stage (C). This is because the insulation<br />

resistance value doubles for a fall in temperature <strong>of</strong> about 10 o C to<br />

15 o C.<br />

3.2.9 Protective Devices<br />

A number <strong>of</strong> protective devices are provided to ensure safe operation <strong>of</strong><br />

traction transformers and other <strong>equipment</strong> (under normal and extended feed<br />

condition with appropriate adjustment <strong>of</strong> settings). Alarm and trip circuit operations<br />

are tele-signalled and indicated at the RCC. The TPC shall in every such case<br />

advise S.S.E., so that he could arrange for the inspection <strong>of</strong> the sub-station to<br />

investigate the cause and take necessary corrective action and submit a detailed<br />

report to Sr. DEE/DEE(TrD).<br />