Head<br />

TABLE 7.8 - GRASS-LINED EMERGENCY SPILLWAY CAPACITY IN CFS<br />

(Side Slopes 4H:1V)<br />

Bottom Width<br />

(ft)<br />

(ft)<br />

8 10 12 14 16 18 20 22 24 26 28 30<br />

0.5 7 8 9 10 12 14 16 18 19 21 23 25<br />

0.6 9 11 12 14 17 19 21 23 25 28 30 32<br />

0.7 11 14 16 19 21 24 26 29 31 34 37 39<br />

0.8 14 17 20 23 26 30 32 35 38 42 45 48<br />

0.9 19 22 25 27 32 36 40 45 49 51 55 59<br />

1.0 22 27 31 35 39 45 48 53 57 61 65 70<br />

1.1 27 32 36 41 47 52 57 60 66 71 76 81<br />

1.2 34 38 45 50 57 61 67 72 78 84 90 96<br />

1.3 38 45 50 57 64 73 79 89 91 98 106 110<br />

1.4 43 51 58 66 75 81 89 95 102 109 117 125<br />

1.5 50 58 67 74 84 93 100 110 118 125 134 143<br />

1.6 57 71 75 83 92 100 113 121 131 141 149 159<br />

1.7 63 75 85 95 106 115 124 133 144 155 164 175<br />

1.8 73 88 95 106 116 129 137 149 160 173 183 194<br />

1.9 80 92 104 114 128 141 152 165 176 188 200 213<br />

2.0 89 102 113 127 140 153 167 180 191 205 217 230<br />

2.1 96 112 125 140 154 168 186 195 207 223 238 253<br />

2.2 105 122 137 153 168 183 198 216 229 244 261 274<br />

2.3 119 134 149 166 183 200 215 232 247 266 282 297<br />

2.4 129 146 162 179 198 217 232 252 266 284 302 319<br />

USDA NRCS Engineering Field <strong>Manual</strong><br />

2. An acceptable alternative is the equation for a broad-crested weir:<br />

Q = CLH 1.5<br />

Where this option is used, the maximum value of C should be 2.8. — relatively smooth liners. In<br />

many cases, a smaller C value should be used. The appropriate C value will vary depending<br />

upon the type of liner <strong>and</strong> anticipated flow depth — usually 2.4 to 2.6. Smaller values should be<br />

used for shallower flows over rough surfaces, larger values for deeper flows over smoother<br />

surfaces. The designer should indicate the st<strong>and</strong>ard reference used to determine the C value. L<br />

is the bottom width of the spillway at the crest, <strong>and</strong> H is the depth of flow above the spillway crest.<br />

Note: Manning’s channel equation should not be used to size the control section of the<br />

emergency spillway. However, it should be used to design the outlet channel below the spillway<br />

crest. Include all outlet channel dimensions <strong>and</strong> specifications on the plan drawings <strong>and</strong> provide<br />

supporting calculations in the narrative.<br />

3. The total of the emergency <strong>and</strong> principal spillway capacities for temporary basins should equal or<br />

exceed the required 2 cfs/acre discharge capacity, or be capable of discharging the routed<br />

25-year, 24-hour storm event without encroaching upon the required freeboard. Permanent basins<br />

may require spillways with capacities exceeding 2 cfs/acre. An acceptable alternative to the 2<br />

cfs/acre discharge capacity with 24” freeboard is a discharge capacity capable of h<strong>and</strong>ling the<br />

peak flow from a 100-year, 24-hour storm event — using maximum runoff conditions — while<br />

maintaining 12” of freeboard. The principal spillway should be used to h<strong>and</strong>le as much of the<br />

required discharge capacity as possible. At a minimum, the principal spillway should be designed<br />

to convey the calculated peak flow from a 10-year, 24-hour storm event. Principal spillways of<br />

permanent basins may be required to have greater discharge capacities.<br />

363-2134-008 / March 31, 2012 / Page 198