01.06.2013 Views

Distributed I/O System ET 200S

Distributed I/O System ET 200S

Distributed I/O System ET 200S

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Digital electronic modules<br />

3.20 2RO NO/NC 24 VDC to 48 VDC/5 A, 24 VAC to 230 VAC/5 A digital electronic module (6ES7132-4HB10-0AB0)<br />

3.20 3.20<br />

Properties<br />

Resistive load Voltage Current Operating cycles<br />

(typical)<br />

For inductive load in<br />

accordance with IEC<br />

947-5-1 DC 13/ AC 15<br />

24 VDC<br />

2.0 A<br />

1.0 A<br />

0.1 million<br />

0.2 million<br />

0.5 A 0.5 million<br />

60 VDC 0.5 A 0.2 million<br />

120 VDC 0.2 A 0.5 million<br />

48 VAC 1.0 A 0.7 million<br />

60 VAC 1.0 A 0.5 million<br />

120 VAC<br />

2.0 A 0.1 million<br />

1.0 A 0.3 million<br />

0.5 A 1 million<br />

0.1A 2 million<br />

For inductive load in 230 VAC<br />

2.0 A 0.1 million<br />

accordance with IEC<br />

947-5-1 DC 13/ AC 15<br />

1.0 A<br />

0.5 A<br />

0.3 million<br />

1 million<br />

2RO NO/NC 24 VDC to 48 VDC/5 A, 24 VAC to 230 VAC/5 A digital<br />

electronic module (6ES7132-4HB10-0AB0)<br />

• Digital electronic module with two relay outputs<br />

• Output current 5 A per output<br />

• Replacement value<br />

• Suitable for solenoid valves, DC contactors, and indicator lights<br />

• Isolated from the supply voltage<br />

• NO and NC contact<br />

General terminal assignment<br />

Note<br />

If you connect an extra-low voltage system (SELV/PELF) on one channel of the relay<br />

subassembly, you can only use an extra-low voltage system (SELV/PELF) on the other<br />

channel.<br />

<strong>ET</strong> <strong>200S</strong><br />

Manual, 12/2005, A5E00514527-03 3-81